Mitsubishi Electric Lossnay LGH-150RVXT-E Installation Instructions Manual page 22

Energy recovery ventilator
Hide thumbs Also See for Lossnay LGH-150RVXT-E:

Advertisement

Function settings (continued)
No.63
External fan speed input setting (0 - 10 VDC)
Set external fan speed input setting.
DIP-SW
Setting
check
SW No.
Setting
Function No. Setting Data
-
-
2-3 OFF
2-6 OFF
SW2-3
2-3 ON
63
SW2-6
2-6 OFF
2-3 OFF
2-6 ON
2-3 ON
2-6 ON
Lossnay changes fan speed according to input voltage to CN26.
speed from remote controllers.
Lossnay operate at weaker fan speed. (Connection example: if you
use a CO
2
use a CO
2
Lossnay changes fan speed as the table below. (Connection
Fan speed
0 - 1.0
-
1.5 - 2.5
1
3.5 - 4.5
2
3
4
No.100
Initialization
All settings which are changed by users are cancelled.
DIP-SW
Setting
check
SW No.
Setting
Function No. Setting Data
-
-
N/A
100
-
-
Setting
External fan speed
check
control using CN26
0
DIP-SW priority
External fan speed
1
control is N/A.
2
3
4
Fan speed changing from
Available
Not available
Not available
Not available
Not available
Setting
check
0
N/A
1
Available
Eng-21