Bcg Internal Wiring Diagram - Westerbeke 3.0 BPMG Operator's Manual

Single phase / 60hz and 50 hz gasoline generators
Table of Contents

Advertisement

BCGBACKEND
COMPONENTS
(TOP VIEW)
.
GROOND~
·
.
.CAPACITOR
IBESE COMPONENTS
ARE LOCATED ON THE
. ROTOR
.
. AC TERMINAL BLOCK
-$;i
WllllJINtl RESISTAflCE (Measured at 200C/68'F)
.
.
60 Hertz Models : Stator Winding 0.93 Ohm/winding.
50 Hertz Models : Stator Winding 1.35 Ohm/winding.
Rotor Winding -
4~0
Ohm
Rotor Winding - 4.0 Ohm
Excitor Winding - 2.0 Qhm
Excitor Winding .. 2.5 Ohm
Capacitor Rating - 34 uF
Capacitor Rating - 31.55 uF
BCG INTERNAL.WIRING DIAGRAM
·GREEN
ROTOR
STATOR
·YELLOW
EXCITOR
OR
I
BROWN
I
•N.WHITE
WHITE
I - .
ri
'12ov·
1· -.
THERMISTER .
I
!i
RED
RED
luiA
K.
61~
'
.
I
:1
,
BLACK
:I
I
BLUE
:I
CAPACITOR
;1
,I!
'
. ' '
·.
.
BY-PASSING THE OVERSPEED BOARD
An
unwanted shutdown or if the engine runs 10-15 seconds
and then shuts down can be caused by a faulty over-speed
board.
1. Refer
to
the Wtting Diagram in this manual.
2. Unplug the brown
#6 wire
that connects between pin #12
of the 15 pin plug connector and the ignition module. The
wire
plug connection is in the harness between the two
components.
3. Without unplugging any connections on the coil relay,
· place a jumper between connection #30 and #87.
4. Manually controlling #30 and #87, start the engine
physically controlling the actuator/throttle keeping the
engine speed at a low comfortable range. H the engine
continues to run more than 15 seconds, a faulty overspeed
board
exists.
NOTE:
The above should only be perfonned as a test. The
generator with a by-passed overspeed board should not be
run under nonnal use. This can present a hazard.
Engines & Generators