Panasonic S-60PT2R5A Installation Instructions Manual page 14

Single split air conditioner
Hide thumbs Also See for S-60PT2R5A:
Table of Contents

Advertisement

How to connect wiring to the terminal
■ For stranded wiring
(1) Cut the wire end with cutting pliers,
then strip the insulation to expose the
stranded wiring about 10 mm and
tightly twist the wire ends. (Fig. 4-7)
(2) Using a Phillips head screwdriver,
remove the terminal screw(s) on the
terminal board.
(3) Using a ring connector fastener or pliers,
securely clamp each stripped wire end
with a ring pressure terminal.
(4) Place the ring pressure terminal, and
replace and tighten the removed terminal
screw using a screwdriver. (Fig. 4-8)
■ examples of shield wires
(1) Remove cable coat not to scratch braided shield. (Fig. 4-9)
(2) Unbraid the braided shield carefully and twist the
unbraided shield wires tightly together. Insulate the shield
wires by covering them with an insulation tube or wrapping
insulation tape around them. (Fig. 4-10)
(3) Remove coat of signal wire. (Fig. 4-11)
(4) Attach ring pressure terminals to the signal wires and the
shield wires insulated in Step (2). (Fig. 4-12)
■ Wiring
T2 type
Remote control wiring and inter-unit control wiring inlet port
* Insert the remote control wiring and
inter-unit control wiring into the electrical
component box from the inlet port as shown
in the figure. This is done regardless of
whether the wiring was inserted from the
top, rear, or left side of the main unit.
Functional ground screw (Schedule Timer)
Clamp
Power wiring
Use this screw when connecting the shield
for the Inter-unit control wiring to ground.
Protective ground screw
Stranded wire
Remote Control Wiring
Inter-unit Control Wiring
Power inlet port
Clamp
Special
washer
Ring
pressure
terminal
Wire
Fig. 4-7
How to carry out power supply wiring
(1) Wiring connection ports
The power inlet port is located at the rear.
The remote control wiring inlet port is located at the rear (for
use with the wired remote controller). For details, refer to
Fig. 3-3.
(2) How to carry out wiring
● Insert the power wiring into the indoor unit through the
rubber at the side of the electrical component box.
● For wiring connection to the outdoor unit and remote
control wiring, open the elongated hole of the piping cover
and pass the wires through the hole.
N OTE
Be sure to use sealing putty to seal off the opening to
prevent dust.
14
Screw
Ring pressure
terminal
Terminal board
Wire
Fig. 4-8
Fig. 4-9
Insulation tape
Shield mesh
Fig. 4-10
Insulation tape
Shield mesh
Fig. 4-11
Fig. 4-12
F616394  15/25
Screw and
Special washer
Ring
pressure
terminal

Advertisement

Table of Contents
loading

This manual is also suitable for:

S-100pt2r5aS-71pt2r5aS-125pt2r5aS-140pt2r5a

Table of Contents