Spacing requirements
A
A
A: 1500 mm (59 inch) or more
CAUTION
• The indoor unit must be installed according to the
specified distances in order to permit accessibility
from each side, to guarantee correct operation,
maintenance, and repair of the unit.
The components of the indoor unit must be reachable
and removable under safe conditions for people and
the unit.
• Do not hold the discharge while carrying the indoor
unit to avoid the possibility of breakage.
• You must hold the hanger plate on the corner and
carry the indoor unit.
Step 3 Optional: Insulating the body of
the indoor unit
If you install a cassette type indoor unit on the ceiling
when temperature is over 27°C (80.6°F) and humidity is
over 80%, you must apply an extra 10mm (3/8 inch) thick
polyethylene insulation or a similar type of insulation to
the body of the indoor unit.
Cut away the part where pipes are pulled out for the
A
insulating work.
Insulate the end of the pipe and some curved area by
using separate insulator.
A

Step 4 Installing the indoor unit

When deciding on the location of the air conditioner the
following restrictions must be taken into account.
1 Place the pattern sheet on the ceiling at the spot
• Since the diagram is made of paper, it may shrink
2 Insert bolt anchors, use existing ceiling supports or
Hole in anchor
Hole in plug
where you want to install the indoor unit.
NOTE
or stretch slightly due to temperature or humidity.
For this reason, before drilling the holes, be sure
to maintain the correct dimensions between the
markings.
construct a suitable support as shown in figure.
Concrete
Suspension bolt (ø9.52(3/8") or M10)
Insert
7