Friedrich MD24Y3J Svc Manual page 73

Single zone air conditioner
Hide thumbs Also See for MD24Y3J:
Table of Contents

Advertisement

Display
Title
code
C/T
40
Sensor Error
WARNING
Before checking PCB or each outdoor electric parts, wait for 3 minutes after the power is off. When measuring at standby state
of power supply, after checking the measurement mode of the meter, be careful of the short-circuits with other parts.
n Error Diagnosis and Countermeasure Flow Chart
n Error Diagnosis and Countermeasure Flow Chart
Is input voltage normal ?
Yes
Is Inverter PCB Normal?
Yes
Recheck power and
installation condition
Check Point
1. Check the Input Voltage (L1- L2 ' 230V±10%)
2. Check Input Voltage Sensor output voltage (2.5Vdc±10%)
< Input Power Source Check Point >
Only for training and service purposes
Cause of error
• Initial current error
No
Check L~N Voltage is 230V±15%
No
Replace inverter PCB assembly
- 73 -
Check point & Normal condition
• Malfunction of current detection circuit.
(Open / Short)
• Check CT Sensor output voltage :
2.5Vdc ±5%