Friedrich MD24Y3J Svc Manual page 63

Single zone air conditioner
Hide thumbs Also See for MD24Y3J:
Table of Contents

Advertisement

Display
Title
code
Input voltage
25
n Error Diagnosis and Countermeasure Flow Chart
Is input voltage normal ?
Yes
Is Inverter PCB Normal?
Yes
Recheck power and
installation condition
Check Point
1. Check the Input Voltage (L1- L2 ' 230V±10%)
2. Check Input Voltage Sensor output voltage (2.5Vdc±10%)
< Input Power Source Check Point >
Only for training and service purposes
Cause of error
• Abnormal Input voltage
(140Vac , 300Vac)
No
Check L~N Voltage is 230V±15%
No
Replace inverter PCB assembly
- 63 -
Check point & Normal condition
• Check the power source.
• Check the components.