Check Point
1. Check the WCN_P(L),P(N) Connection condition at the Main PCB.(Refer to outdoor wiring diagram)
2. Check the DC Link voltage at not operating(280V↑)
3. Check the DC Link voltage at Comp operating(340V↑)
4. Check DC Link Sensing Signal :2.4~2.8V (Refer the Picture)
* AUUW24GD2 [MR24UY3J]
IN/I
GND
Black
Red
Vdc
<CT Sensing Check Point>
- 61 -