Magic Chef MCSCTE24BG User Manual page 9

24-inch electric cooktop
Table of Contents

Advertisement

Available languages

Available languages

a.
Combustible area above countertop
b.
Recommended upper cabinet width:
24" (61cm)
c.
Recommended upper cabinet depth:
13" (33 cm)
d.
30" (76.2 cm) minimum clearance
between top of cooktop platform and
bottom of uncovered wood or metal
cabinet (24" [61 cm] minimum
clearance if bottom of wood or metal
cabinet is covered by not less than 1/4"
[0.6 cm] flame retardant millboard
covered with not less than No. 28 MSG
sheet steel, 0.015" [0.04 cm] stainless
steel, or 0.024" [0.06 cm] aluminum or
0.020" [0.05 cm] copper)
e.
Recommended cutout depth: 19-1⁄4" (49.0 cm) The cooktop will fit in cutout from 19-1/8" to 19-5/16" (48.6
to 49.0 cm).
f.
Recommended cutout width: 22" (56.0 cm) The cooktop will fit in cutout from 21-7/8" to 22-1/8" (55.6 to
56.2 cm).
g.
Minimum distance from top of countertop to junction box or outlet: 7" (17.8 cm)
h.
Maximum distance from right side of cabinet to junction box or outlet: 9" (23.0 cm) .
i.
Minimum clearance from upper cabinet to countertop within minimum horizontal clearances to cooktop:
18" (45.7 cm)
j.
Minimum clearance between front edge and countertop: 2" (5.1 cm)
k.
Minimum distance to nearest left and right side combustible surface above cooktop: 2" (5.1 cm)
l.
Minimum clearance between back wall and countertop: 2" (5.1 cm)
NOTE: If cabinet has a drawer, a 5-1/2" (14.0 cm) depth clearance from the top of the countertop to the top of
the drawer (or other obstruction) in base cabinet is required.
ELECTRICAL REQUIREMENTS
WARNING: Electrical Shock Hazard
Disconnect power before servicing.
Use 8 gauge copper wire.
Electrically ground cooktop.
Failure to follow these instructions can result in death, fire, or electrical shock.
If codes permit and a separate ground wire is used, it is recommended that a qualified technician determine that
the ground path and wire gauge are in accordance with local codes.
Check with a qualified technician if you are not sure the cooktop is properly grounded.
Make sure that the electrical connection and wire size are adequate and in conformance with the National
Electrical Code, ANSI/NFPA 70-latest edition or CSA Standards C22.1-94, Canadian Electrical Code, Part 1 and
C22.2 No. O-M91-latest edition, and all local codes and ordinances.
b
a
d
l
j
k
9