English – March 2015
Introduction
This installation guide provides instructions for
installation, startup and adjustment. To receive a copy
of the instruction manual, contact your local Sales
Office or view a copy at www.fisherregulators.com. For
further information refer to Type MR108 Instruction
Manual, Form 5875, D103247X012.
P.E.D. Category
This product may be used as a pressure accessory
with pressure equipment in the following Pressure
Equipment Directive 97/23/EC categories. It may
also be used outside of the Pressure Equipment
Directive using sound engineering practice (SEP)
per table below.
PRODUCT SIZE
DN 25 / NPS 1
DN 50 / NPS 2
DN 80 / NPS 3
DN 100 / NPS 4
Specifications
Available Constructions
Type MR108 with low-pressure actuator:
Direct-operated large multi-purpose backpressure
regulator with 0.34 to 2.4 bar / 5 to 35 psig
pressure range
Type MR108 with high-pressure actuator:
Direct-operated large multi-purpose backpressure
regulator with 1.7 to 20.7 bar / 25 to 300 psig
pressure range
Body Sizes and End Connection Styles
DN 25 and 50 / NPS 1 and 2:
NPT, CL125 FF, CL250 RF, CL150 RF, CL300 RF,
CL600 RF and PN 16/25/40 RF
DN 80 and 100 / NPS 3 and 4:
CL125 FF, CL250 RF, CL150 RF, CL300 RF,
CL600 RF and PN 16 RF
Backpressure Control Ranges
Low-Pressure Actuator:
0.34 to 0.97 bar / 5 to 14 psig; 0.55 to 1.7 bar /
8 to 24 psig; 0.83 to 2.1 bar / 12 to 30 psig;
1.0 to 2.4 bar / 15 to 35 psig
High-Pressure Actuator:
1.7 to 2.8 bar / 25 to 40 psig; 2.4 to 4.8 bar /
35 to 70 psig; 3.8 to 8.3 bar / 55 to 120 psig;
6.2 to 13.8 bar / 90 to 200 psig
175 to 300 psig
(3)
1. The pressure/temperature limits in this Installation Guide or any applicable limitation should not be exceeded.
2. Maximum set pressure is limited to 10.3 bar / 150 psig for constructions with Fluorocarbon (FKM) diaphragm.
3. Not applicable for constructions with Fluorocarbon (FKM) diaphragm.
4. Fluorocarbon (FKM) is limited to 93°C / 200°F hot water.
5. Maximum Inlet, Outlet and Emergency Casing Pressures for constructions with Fluorocarbon (FKM) diaphragm are limited to 15.8 bar / 230 psig or the body rating limit, whichever is lower.
6. Ethylene Propylene (EPDM) is limited to -7 to 107°C / 20 to 225°F when used with Low Pressure Actuator.
7. Pressure ratings are based on a maximum operating temperature of 121°C / 250°F.
CATEGORY
SEP
II
II
II
(1)
; 12.1 to 20.7 bar /
(2)
www.fisherregulators.com
Maximum Set Pressure
Low-Pressure Actuator: 2.4 bar / 35 psig
High-Pressure Actuator:
Nitrile (NBR) and Ethylene Propylene (EPDM)
Diaphragm: 20.7 bar / 300 psig
Fluorocarbon (FKM) Diaphragm:
10.3 bar / 150 psig
Temperature Capabilities
Nitrile (NBR): -29 to 82°C / -20 to 180°F
Fluorocarbon (FKM): -7 to 121°C / 20 to 250°F
Ethylene Propylene (EPDM): -29 to 107°C /
-20 to 225°F
(6)
Maximum Emergency Casing Pressures
Low-Pressure Actuator: 4.8 bar / 70 psig
High-Pressure Actuator: 27.6 bar / 400 psig
Maximum Inlet Pressures
Low-Pressure Actuator: 4.8 bar / 70 psig
High-Pressure Actuator: 27.6 bar / 400 psig
Maximum Outlet Pressures
Low-Pressure Actuator: 4.8 bar / 70 psig
High-Pressure Actuator: 27.6 bar / 400 psig
Maximum Differential Pressures
Low-Pressure Actuator: 4.8 bar / 70 psig
High-Pressure Actuator: 27.6 bar / 400 psig or
maximum inlet pressure, whichever is lower
Maximum Pressures over Set Pressure to Avoid
Internal Parts Damage
Low-Pressure Actuator: 1.4 bar / 20 psig
High-Pressure Actuator: 8.3 bar / 120 psig
Installation
WARNING
!
Only qualified personnel should
install or service a backpressure
regulator. Backpressure regulators
should be installed, operated and
maintained in accordance with
international and applicable codes
and regulations and Emerson Process
Management Regulator
Technologies Inc. instructions.
If using a backpressure regulator
on a hazardous or flammable fluid
service, personal injury and property
damage could occur due to fire or
explosion of vented fluid that may
Type MR108
(1)
(1)
(1)(7)
(1)(7)
(1)(7)
(1)
(1)
(4)
(5)
(5)
(5)

Advertisement

loading

Summary of Contents for Emerson FISHER MR108 Series

  • Page 1 Backpressure Control Ranges international and applicable codes Low-Pressure Actuator: and regulations and Emerson Process 0.34 to 0.97 bar / 5 to 14 psig; 0.55 to 1.7 bar / Management Regulator 8 to 24 psig; 0.83 to 2.1 bar / 12 to 30 psig;...
  • Page 2 Type MR108 have accumulated. To prevent such Note injury or damage, provide piping or It is important that the backpressure tubing to vent the fluid to a safe, regulator be installed so that the vent well-ventilated area or containment hole in the spring case is unobstructed vessel.
  • Page 3 Type MR108 Parts List Description Valve Body Body Flange SEE DETAIL V Stud Bolt DN 25 / NPS 1 (4 required) DN 50, 80 and 100 / NPS 2, 3 and 4 (8 required) Gasket Valve Spring Cage Port Seal Seat Ring Piston Ring Upper Seal...
  • Page 4 For further information visit www.fisherregulators.com The Emerson logo is a trademark and service mark of Emerson Electric Co. All other marks are the property of their prospective owners. Fisher is a mark owned by Fisher Controls International LLC, a business of Emerson Process Management.