Raychem TRACETEK TT3000 SERIES Installation Instructions Manual

Modular sensing cables

Advertisement

Quick Links

TT3000 and TT5000 Series
Modular Sensing Cables Installation Instructions
COMPLETE BILL OF MATERIALS
Before beginning installation, confirm there is a plan
for the leak detection system layout, and a complete
bill of materials. In addition to sensing cables, the leak
detection bill of materials should include a TraceTek
alarm module, leader and/or jumper cables, mapping
(TT-TAG), and various other components, such as
Modular Branching Connectors, (TT-MBC-MC).
General Notes—Do's and Don'ts
Do
• Store the sensing cable in its original container in
a clean, dry area prior to installation.
• Schedule sensing cable installation after major
construction work (which could damage or
contaminate the cable) has been completed.
• Clean the area where sensing cable is to be
installed and remove any debris or other source
of contamination.
• Replace TT5000 series hydrocarbon sensing
cable once it has contacted a solvent or fuel.
GENERAL INFORMATION
These instructions explain the proper procedures for installing and testing nVent
RAYCHEM TraceTek TT3000 and TT5000 series modular and zone sensing
cables, and provide specifics for sumps, subflooring, and containment trenches.
For double-containment pipe applications, refer first to the TraceTek
Double-Containment Installation Guide (LIT-138); for double-wall tank
applications, refer first to the General Instructions for TraceTek Installation in
Double-Wall Tanks (H55313).
The General Installation Instructions for TraceTek Environmental Applications
(H55523) provides an overview of the installation process for the TraceTek system,
and refers to detailed instructions for each step.
To obtain copies of installation instructions, consult nVent at (650) 216-1526.
TOOLS AND MATERIALS FOR INSTALLATION AND TESTING
• TT-PTB-1000 Portable Test Box with adapters or ohmmeter
(20-MW range or greater)
• TT-ULTRATORCH flameless heating tool or appropriate heat gun.
• TT-MLC-MC Modular Leader Cable (needed for testing with ohmmeter)
• TT-MET-MC Modular End Terminations (not needed for zone cables)
ADDITIONAL MATERIALS FOR SUMP, CONTAINMENT TRENCH,
OR SUBFLOOR APPLICATIONS:
• For TT3000 sensing cable: TT-HDC-1/4 or TT-HDC-1/4-200-NA
Hold-Down Clips
• For TT5000 series sensing cables:
TT-HDC-1/2-NA-50 hold-down clips
• 3M-type 1300 or 08001 adhesive (obtained locally) for hold-down clips
with no adhesive (not required for TT-HDC-1/4)
• Drag sensing cable through contaminants (such as pipe dope, PVC cement, solvents, oil, dirt).
• Use damaged or contaminated sensing cable.
• Solder or weld near the cable without protecting it from heat, flux, and splatter.
• Use pulling lubricants to install TraceTek sensing cables.
• Drop tools or sharp or heavy objects onto the cable.
• Pull the sensing cable with excessive force (more than 50 pounds/20 kg).
• Place TT5000 series sensing cable where it is subject to pinching or pressure, as this will trigger
an alarm.
• Subject TT5000 series sensing cable to temperatures higher than 80°C (176°F).
• Use adhesive tapes or clamping devices to secure the sensing cable.
• Allow cable connectors to become wet, dirty, or contaminated.
Don't

Advertisement

loading

Summary of Contents for Raychem TRACETEK TT3000 SERIES

  • Page 1 GENERAL INFORMATION These instructions explain the proper procedures for installing and testing nVent RAYCHEM TraceTek TT3000 and TT5000 series modular and zone sensing cables, and provide specifics for sumps, subflooring, and containment trenches. For double-containment pipe applications, refer first to the TraceTek Double-Containment Installation Guide (LIT-138);...
  • Page 2 General Layout of TraceTek System Modular branching connector Modular jumper cable (TT-MBC-MC) Modular sensing cable Modular leader cable (TT-MLC-MC) TraceTek alarm Modular jumper cable module (several (TT-MJC-xxx-MC) models available; TTDM alarm and locating module Modular is shown) sensing cable Note: •...
  • Page 3 2. Check each length of sensing cable before installation. To ensure that each length of sensing cable is intact and free of contamination, follow the Sensing Cable Test Procedure detailed on page 6. Do not use damaged or contaminated sensing cable. 3.
  • Page 4 5. Complete the system. • Install other TraceTek components (such as Modular Modular Branching Connector Connector Branching Connectors, Weighted Lengths, and Modular (shows after middle leg) with pins Jumper Cables) as called for in the system layout. toward module Complete the sensing circuit. •...
  • Page 5 Sensing Cable Test Procedure Method with TraceTek Portable Test Box (PTB) Testing a string of cables 1. Ensure the end termination is connected to the sensing cable. If checking several lengths of sensing cable in series (a cable string), ensure they are all connected. End termination 2.
  • Page 6 North America Asia Pacific Tel +86.21.2412.1688 Tel +1.800.545.6258 Fax +86.21.5426.3167 Fax +1.800.527.5703 cn.thermal.info@nvent.com thermal.info@nvent.com Latin America Europe, Middle East, Africa Tel +1.713.868.4800 Tel +32.16.213.511 Fax +1.713.868.2333 Fax +32.16.213.604 thermal.info@nvent.com thermal.info@nvent.com nVent.com ©2018 nVent. All nVent marks and logos are owned or licensed by nVent Services GmbH or its affiliates. All other trademarks are the property of their respective owners. nVent reserves the right to change specifications without notice.

This manual is also suitable for:

Tracetek tt5000 series