General Layout of TraceTek System
TraceTek alarm
module (several
models available;
TTDM alarm and
locating module
is shown)
Note:
• D rawing not to scale.
• Not shown: heat-shrinkable tube
to cover each connection.
Modular Sensing Cable   (with factory-installed connectors)
Installation Steps
1. Prepare the area where the sensing cable will be located.
• Verify that major construction is complete.
• Clean the area where the cable will be installed to remove
debris and sources of contamination. For techniques in
double-containment piping, consult the TraceTek
Double-Containment Installation Guide (LIT-138).
• For sumps, containment trenches, and subfloor applications,
install TraceTek hold-down clips. For TraceTek TT3000 sensing
cables, use 1/4" hold-down clips (TT-HDC-1⁄4...); for TraceTek
TT5000 series sensing cables, use 1/2 inch hold-down clips
(TT-HDC-1⁄2-NA-50).
Clean the floor surface where hold-down clips will be placed so
adhesive can work properly.
Position hold-down clips so the sensing cable will provide the
desired leak detection coverage. To best secure the cable,
alternate the direction of the hold-down clips, and install them
at intervals of no greater than 6 feet (2 m) and at every change
in direction (at sides of trench, for example).
2 | nVent.com
Modular leader cable
(TT-MLC-MC)
Modular jumper cable
(TT-MJC-xxx-MC)
Factory-installed connector
Heat-shrinkable tube
(for extras, order TT-COS)
supplied with cable
Modular sensing cable
(TT3000-xxx-MC or
TT5000-xxx-MC or
TT5001-xxx-MC)
Modular end termaination
TT-ME T-MC
Modular branching connector
(TT-MBC-MC)
Modular
sensing
cable
Zone Sensing Cable
Factory-installed
end termination
Important: Let the adhesive dry per manufacturer's
recommendation before proceeding with sensing-cable
installation.
• In sumps that may collect water, mount TT5000 series sensing
cable vertically to allow it to detect hydrocarbons floating on water;
prepare for this by installing hold-down clips up side of sump.
TT-HDC-1⁄4 or
TT-HDC-1/4-200-NA
Modular jumper cable
Modular sensing cable
(with factory-installed connector and end
termination)
Factory-installed connector
Heat-shrnkable tube
(for extras, order TT0COS)
supplied with cable
Modular sensing cable
(TT3000-ZONE-MC or
TT5000-ZONE-MC or
TT5001-ZONE-MC)
TT-HDC-1⁄2-NA-50
< 6 ft (2 m)