Installation

4.11.3.5.1 FII-DO

Label
14. Ry1_a
15. Ry1_b
16. Ry2_a
17. Ry2_b
18. Ry3_a
19. Ry3_b
20. Ry4_a
21. Ry4_b

4.11.3.5.2 FII-DO - Overfill Protection

Label
48. Ofp_a
49. Ofp_b

4.11.3.6 HCI-HAO

Cable specifications
Type
Maximum length
Label
46.
47.
Installation Guide
36
Parameters
Vmax = 125 Vac, Imax = 0.5 A
Vmax = 110 Vdc, Imax = 0.3 A
Pmax = 30 W
NO/NC by factory jumper
Vmax = 125 Vac, Imax = 0.5 A
Vmax = 110 Vdc, Imax = 0.3 A
Pmax = 30 W
NO/NC by factory jumper (default = NO)
Vmax = 250 Vac, Imax = 3 A
Vmax = 40 Vdc, Imax = 3 A
Pmax = 750 W
NO/NC by factory jumper
Vmax = 250 Vac, Imax = 3 A
Vmax = 40 Vdc, Imax = 3 A
Pmax = 750 W
NO/NC by factory jumper
Parameters
Vmax = 250 Vac, Imax = 3 A
Vmax = 40 Vdc, Imax = 3 A
Pmax = 750 W
NO/NC by factory jumper
Shielded twisted pair
1200 meter
Parameters
4-20 mA +
4-20 mA -
SmartRadar FlexLine
Part No.: 4417.760_Rev06