7.
D
IMENSIONS AND SERVICE SPACE

7.1. Dimensions of the outdoor unit

20
22
360
107
Unit of measurement: mm

7.2. Service space of the outdoor unit

The space around the unit is adequate for servicing and the minimum
space for air inlet and air outlet is available. (Refer to the figure
below).
>50
Unit of measurement: mm
NOTICE
The wall height on the air outlet side (marked with grey
arrow in the figure above) must be less than 1200 mm.
The installation space required on this drawing is for full load heating
operation without considering possible ice accumulation.
If the location of the installation is in a cold climate, then all
dimensions above should be >500 mm to avoid accumulation of ice in
between the outdoor unit and the nearest walls.
The connection piping outlet direction in the installation shown in
the figure is frontward or downward.
When routing the piping backward, secure space of ≥250 mm on
the right side of the unit.
NOTICE
(*) If shut off valves are directly installed on the water inlet
and outlet, increase installation space at the rear of the
unit to a minimum of 300 mm.
8.
T
YPICAL APPLICATION EXAMPLES
Refer to the installation manual of the EKCB(X/H) indoor unit.
EBHQ006+008BAV3
Unit for air to water heat pump system
4PW64602-1D – 12.2010
1189
84
1170
>150
9.
I
,
NSPECTING
HANDLING AND UNPACKING
THE UNIT

9.1. Inspection

At delivery, the unit must be checked and any damage must be
reported immediately to the carrier's claims agent.

9.2. Handling

The unit is packed in a cardboard box fixed by straps.
When handling the unit, take into account the following:
1
Fragile, handle the unit with care
Keep the unit upright in order to avoid compressor damage.
2
Choose on before hand the path along which the unit is to be
brought in.
3
Bring the unit as close as possible to its final installation position
in its original package to prevent damage during transport.
4
After unpacking, the unit can be positioned correctly using the
handles provided at both ends of the unit.
As shown in the figure below, slowly move the unit by grabbing
the left and right grips. Position your hands on the corner instead
of grabbing the suction grill, otherwise the casing could be
deformed.
CAUTION
To avoid injury, do not touch the air inlet or aluminium fins
of the unit.
Installation manual
9

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ebhq008bav3

Table of Contents