Download Print this page

Greenheck MSXX04 Series Installation Instructions page 3

Advertisement

INSTRUCTIONS
Power Consumption
Model
Volts
MS4104
120
MS4109
120
MS4604
230
MS4609
230
MS8104
24
MS8109
24
Our Commitment
As a result of our commitment to continuous improvement, Greenheck reserves the right to change specifications
without notice.
Specific Greenheck product warranties are located on greenheck.com within the product area tabs and in the
Library under Warranties.
®
Phone: (715) 359-6171 • Fax: (715) 355-2399 • E-mail: gfcinfo@greenheck.com • Website: www.greenheck.com
477252• MS Series Rev. 1, October 2013
Running
Holding
18W
9W
23W
7W
18W
11W
23W
7W
16VA
8VA
23VA
7VA
FATPA DIRECT DRIVE SERIES
Actuator Weight
5 lb (2.3 kg).
Noise Rating
Driving Open: Maximum 80 dBA at 1m.
Holding: Maximum 20 dBA at 1m (no audible noise).
Temperature Ratings
Ambient: 0°F to 130°F (-18°C to 55°C)
Shipping and Storage: -40°F to 140°F (-40°C to 60°C)
Humidity Ratings
5% to 95% RH non-condensing.
Environmental Protection Ratings
NEMA 1
IP40
Approvals
Underwriters Laboratories Inc. UL 873 plenum rating,
and UL/cUL.
Actuator Timing (Under Load)
Drive Open: 15 seconds.
Spring Close: 15 seconds.
Copyright 2013 © Greenheck Fan Corporation