Typical Installation - Coleman LX SERIES Technical Manual

Split system heat pumps 16 seer – r-410a – 1 phase 2 thru 5 nominal tons
Hide thumbs Also See for LX SERIES:
Table of Contents

Advertisement

TYPICAL INSTALLATION

CAUTION: Special care must be taken to avoid recirculation of discharge air through condenser coil.
48" OVERHEAD CLEARANCE
10" CLEARANCE
AROUND PERIMETER
(6" clearance
permissible on one
side only, see
Alternative
Installation
Clearances.)
NOTE:
Ensure a minimum of
24" clearance between
any two units.
Care must be taken to prevent ice from damaging the unit. Damage may occur from ice falling onto unit from a sloped roof or from a vertical drip
line due to a partial overhang.
Johnson Controls Unitary Products
NEC CLASS 1 WIRING
WEATHERPROOF
DISCONNECT
SWITCH
CONTROL
ACCESS
PANEL
MINIMUM 18" SERVICE ACCESS CLEARANCE
Maintain minimum clearance on one side of access panel.
CAUTION
!
THERMOSTAT
NEC CLASS 2 WIRING
TO FURNACE OR
AIR HANDLER
TERMINAL BLOCK
NEC CLASS 2 WIRING
NOTE:
All outdoor wiring
must be weatherproof.
SEAL OPENINGS
Use permagum or equivalent.
5186825-CTG-D-0717
NOTE:
Ensure adequate
wall support.
3 BRACES
Use for wall mount with
center brace under
center of compressor.
5 SNOW PUMP-UPS
Use in deep snow areas
with fth pump-up under
center of compressor.
A0260-002
55