Before Beginning The Retrofit Process Identify The Breaker And The Retrofit Kit; Following The Icons To A Successful Retrofit; Identifying The K-Line Breaker - Eaton digtrip 510 with zone Interlock Installation, Operation And Maintenance Manual

Table of Contents

Advertisement

IL 33-K2C-3
Before Beginning the Retrofit Process
Identify the Breaker and the Retrofit Kit
It is important to verify exactly which version of ITE
K-Line Breaker(s) is to be Retrofitted and to insure
that the correct Cutler-Hammer Retrofit Kit(s) was
ordered. Each Breaker must be identified using all
of the following sources:
1. Name Plate Information;
2. Back Plate Color;
3. Type of Finger Clusters
(Rectangular or Round); and
4. Fuse Use and Configuration
(Horizontal or Vertical).
Table 2 Identifying the K-Line Breaker
Breaker
Back Plate
1
Rating
Color
Non-Fused
K-1600
Black
K-1600
Red
K-2000
Red
Top Mounted Horizontal and Vertical Fused
2
KDON-
Black
1600
KDON-
Red
1600
KDON-
Red
1600
Bottom Mounted Horizontal Fused
2
KDON-
Black
1600
KDON-
Red
1600
KDON-
Red
1600
NOTES:
1. Black or Red refers to the color of the Breaker Back Plate.
2. If specified during ordering, special Trip Unit Brackets have been supplied for some older models of the
KDON-1600 Black Breaker equipped with trigger fuses. If the Brackets are needed but were not ordered,
contact Cutler-Hammer at: 1-800-937-5487.
GENERAL NOTE:
If the existing Breaker components mandate that the new DTA, supplied with the Retrofit Kit, be mounted inside the
Breaker on the right side instead of the left, as detailed in these instructions, contact Cutler-Hammer at: 1-800-937-5487
to obtain the special parts required. See Step 4 for details.
Effective 10/00
Desired Sensor
Finger Cluster
Location
Type
Top
Rectangular
Top
Rectangular
Top
Round
Bottom
Rectangular
Bottom
Rectangular
Bottom
Round
Top
Rectangular
Top
Rectangular
Top
Round
Please refer to the following table and verify that
the first three (3) characters of the Retrofit Kit
Code Number correspond to the Breaker being
Retrofitted.

Following the Icons to a Successful Retrofit

During certain parts of the Retrofit Process, proce-
dures may differ depending on the version of the
Breaker being Retrofitted. To enable the Retrofitter
to quickly identify the correct procedures for the
Breaker, Icon(s) will appear. Simply follow only the
instructions identified by the Icon for the Breaker
being Retrofitted.
Fuse
Fuse
Location
Configuration
None
N.A.
None
N.A.
None
N.A.
Top
Horizontal
or Vertical
Top
Horizontal
or Vertical
Top
Horizontal
or Vertical
Bottom
Horizontal
Bottom
Horizontal
Bottom
Horizontal
Page 5
Retrofit
ICON
Kit Code
K1C
K2C
K2D
K6C
K4C
K7C
K1C
K2C
K5C

Advertisement

Table of Contents
loading

This manual is also suitable for:

Digitrip 510 basicDigtrip 610Digtrip 910Digtrip 810