Raychem FTC-XC Installation Instructions

Power connection and end seal kit

Advertisement

Quick Links

Approvals
718K Pipe Heating
Certified
Cable, 9J8 6
with XL-Trace,
Radiant Heating
and RaySol
Cable
heating cables
Kit Contents
Item
Qty
Description
A
1
Gel-filled end seal
B
2
Black heat-shrinkable tubes (
C
1
Green/yellow heat-shrinkable tube (
D
1
Black heat-shrinkable tube (
E
1
Cable tie
F
3
Wire nuts
G
2
Warning labels
H
1
RaySol circuit tag
WARNING:
This component is an electrical device that
must be installed correctly to ensure proper
operation and to prevent shock or fire. Read
these important warnings and carefully follow
all the installation instructions.
• To minimize the danger of fire from sustained
electrical arcing if the heating cable is damaged
or improperly installed, and to comply with the
requirements of Tyco Thermal Controls, agency
certifications, and national electrical codes,
ground-fault equipment protection must be used.
Arcing may not be stopped by conventional
circuit breakers.
For XL-Trace
only
APPROVED
For 12XL2-CT,
-CR only
1
in x 5
1
in)
8
2
in x 6 in)
1
4
in x 1 in)
1
2
• Bus wires will short if they contact each other.
Keep bus wires separated.
• Keep components and heating cable ends
drybefore and during installation.
• The black heating cable core is conductive and
can short. It must be properly insulated and kept
dry.
• Component approvals and performance are
based on the use of Tyco Thermal Controls–
specified parts only. Do not use substitute parts
or vinyl electrical tape.
• Leave these instructions with end user
forreference and future use.
FTC-XC
Power Connection and End Seal Kit
Installation Instructions
Description
The Raychem
FTC-XC Power Connection and End Seal Kit is for
®
use with XL-Trace
®
-CR and -CT heating cables installed in conduit
or in direct buried pipe applications, and for RaySol
applications. Materials for one power connection and one end seal
are included in this kit. These installation instructions must be used
in conjunction with the XL-Trace and RaySol System Installation and
Operation Manuals. For technical support contact your Tyco Thermal
Controls representative or call Tyco Thermal Controls at
800-545-6258.
Tools Required
• Utility knife
• Diagonal cutters
Additional Materials Required (not provided in this kit)
• Two UL Listed or CSA Certified junction boxes suitable for the
location, with a clearance hole for
threaded hub. (For RaySol applications, the power connection end
seal may be terminated in a single box, if desired.)
Raychem
RaySol
CIRCUIT POWER
H
SYSTEM 9J86 RADIANT HEATING CABLE
UL LISTING REQURES THHIS TAG BA ATTACHED
WITHIN 3 INCHES OF POER CONNECTION.
FILL IN BLANKS WITH BALL POINT PEN.
OPERATING VOLTAGE_____ HEATING CABLE LENGTH_____
WARNING
G
Fire and Shock Hazard
Self regulating electrical
heating cable attached to this pipe
Disconnect before servicing
Raychem
F
E
CAUTION:
Health Hazard: Overheating heat-shrinkable tubes
will produce fumes that may cause irritation. Use
adequate ventilation and avoid charring or burning.
Consult MSDS RAY3122 for further information.
CHEMTREC 24-hour emergency telephone:
800-424-9300.
Non-emergency health and safety information:
800-545-6258.
®
floor warming
• Needle nose pliers
• Heat gun or propane torch
-inch conduit or
-inch NPT
1
1
2
2
A
B
C
D

Advertisement

loading

Summary of Contents for Raychem FTC-XC

  • Page 1 FTC-XC Power Connection and End Seal Kit Installation Instructions Description The Raychem FTC-XC Power Connection and End Seal Kit is for ® use with XL-Trace ® -CR and -CT heating cables installed in conduit or in direct buried pipe applications, and for RaySol ®...
  • Page 2 FTC-XC Installation Instructions Heating Cable Construction Inner jacket Conductive core Outer jacket Braid Bus wires XL-Trace -CR and -CT RaySol heating cable Power Connection Installation for XL-Trace -CR and -CT, and RaySol Heating Cables 7 in 6 3/4 in Do not cut through braid or inner jacket.
  • Page 3 FTC-XC Installation Instructions • Slip green/yellow tube over braid and shrink. • Center 1 in black shrink tube over end of heating cable as shown. Ground wire • Heat tube evenly until it shrinks and adhesive flows out both ends.
  • Page 4 FTC-XC Installation Instructions End Seal Installation for XL-Trace -CR and -CT, and RaySol Heating Cables • Clearly cut off the end of cable. • Score down and around outer jacket 1 inch from the end. • Remove the outer jacket.