Digital Energy™
3.3.2
Storage of the battery
In case of extended storage, when the delivery includes maintenance free batteries, keep in mind
that they are subject to auto-discharging process
To avoid permanent damages to the battery, you must observe the following instructions:
•
The storage time without charging the battery depends on the temperature of the storage
ambient.
•
The optimal ambient temperature for the batteries is 68°F (20°C).
For storage temperature higher than 68°F (20°C), the storage time will decrease.
•
Each additional 18°F (10°C) over the nominal temperature of 68°F (20°C) will decrease the
storage time, without freshening charge, by half.
In case of a maintenance free battery, the storage time without charging the battery is
approximately:
6 months with storage temperature 68°F (20°C)
3 months with storage temperature 86°F (30°C)
2 months with storage temperature 95°F (35°C)
NOTE !
In case of battery storage pay
attention to:
OPM_LPS_3UI_10K_20K_0US_V010.doc
SENSITIVE
FRAGILE
TO DAMPNESS
Installation Guide LP 33 / 10 - 20 kVA
14/38
g
SENSITIVE
SENSITIVE
TO HEAT
TO FROST