5.2 Potential Free Contact Interface

Four potential free change-over contacts are available for signalling the following alarms to a user
defined system:
• bypass active;
• mains failure;
• battery low;
• general alarm.
Capacity of the relay contacts:

5.3 SNMP Interface (optional)

The optional SNMP plug-in card allows the data interface to be connected directly to an Ethernet
network.

6. OPTIONS

6.1 SNMP Interface Card

An SNMP interface card can be placed in the CardConnect slot at the rear panel of the UPS, and allows the
data interface to be connected directly to an Ethernet network.
When this option is installed the ComProt communication link is no longer available to the user.

6.2 Alarm Boxes

An interface box linked to the ComConnect port, the VIC/RELAYBOX/01 translates the ComConnect signals
to five independent changeover contacts, with a maximum switching capacity of 230V/5A each.
Wall mounted plastic alarm boxes are available for remote audible and visual alarm indication.

6.3 Connectivity Products

A splitter box translates information from the ComConnect to several computers.
Interface kits (cables and software) are available for UPS communication with most commonly used
network operating systems, including Novell, UNIX, VMS, Banyan Vines, Windows 3-95-98-NT, Apple,
3COM, IBM LANserver, IBM AS/400.
Please contact your dealer for specific information.

6.4 Battery Extension Packs

Extended run-time versions are equipped with additional batteries to increase the autonomy time of the
unit.
These additional batteries are housed in a separate battery cabinet and are connected in parallel.
Additional batteries will increase the recharging time for the unit.
Modifications reserved
PRD_LPS_31E_8K0_20K_1GB_V021.doc
Nom:
48V 500mA
Min:
5V 100mA