Smith Cast Iron Boilers
Chassis
Boiler
Burner
Spec.
HE28-4
CF1400
BCF205
HE28-5
CF2300A
BCF304
HE28-6
CF2300A
BCF304
HE28-7
CF2300A
BCF304
HE28-8
CF2500
BCF1801
HE28-9
CF2500
BCF1801
HE28-10
CF2500
BCF1801
HE28-11
CF3500A
BCF1301
HE28-12
CF3500A
BCF1301
HE28-13
CF3500A
BCF1301
Utica Boiler
Chassis
Boiler
Burner
Spec.
SFM66
CF500
BCF809
SFM77
CF500
BCF809
6225
CF375
BCF3907
7275
CF375
BCF3907
HE28
High
Fire
Air Tube
Combination
Rate
Nozzle
CF66KF
7.80
4.50x45P
CF66KG
9.50
5.50x60P
CF66KG
11.20
6.50x60P
CF66KG
13.90
8.00x60P
CF66KP
16.40
5.00x45P
CF66KP
18.20
5.50x45P
CF66KP
20.80
6.00x60P
CF92KM
22.50
6.50x60P
CF114KR
25.10
7.50x60P
CF114KR
27.50
8.00x60P
Starfire II
High
Air Tube
Fire
Rate
Combination
Nozzle
CF60KK
2.25
2.00x60B
CF60KK
2.75
2.50x60B
CF100KZ
2.25
2.00x45B
CF100KZ
2.75
2.25x45B
Series Boiler
Blue -
Red -
Low Fire
High Fire
Air or
Air or
Head
Setting
Shutter
Band
2
35
45
0
18
28
3
25
35
6
30
40
1
15
25
5
20
35
7
21
45
4
24
50
5
27
70
6
30
70
Shutter and band settings refer to the AFG, CF375, CF500 and CF800 only.
Series Boiler
Blue -
Red -
Low Fire
High Fire
Head
Air or
Air or
Shutter
Band
Setting
1
3
0
2-1/2
5-1/2
0
0
6
3
1
4
5
Shutter and band settings refer to the AFG, CF375, CF500 and CF800 only.
Low Fire
High Fire
Pressure
Pump
Pump
Firing
Press.
Press.
Flange
150
300
51629
150
280
51630
150
300
51630
150
280
51629
270
270
51630
280
280
51630
300
300
51630
300
300
51630
290
290
51631
290
290
51631
Low Fire
High Fire
Pressure
Pump
Pump
Firing
Press.
Press.
Flange
N/A
140
51311
N/A
140
51311
N/A
140
51311
N/A
140
51311
Page 28
Insertion
3.875"
3.875"
3.875"
3.875"
3.875"
3.875"
3.875"
4.50"
5.50"
5.50"
Insertion
1.50"
1.50"
2.250"
2.25"

Advertisement

loading

This manual is also suitable for:

Cf2300aCf2500aCf3500aCf375Cf500Cf800 ... Show all