Download Print this page

Mitsubishi FX3G series Installation Manual page 2

Hide thumbs Also See for FX3G series:

Advertisement

3.2 Wiring of Analog Output
→ For the terminal configuration, refer to Section 1.2
Using voltage
1DA-BD
Terminal
output
block
V+
I+
VI-
Grounding
Using current
1DA-BD
Terminal
output
block
V+
I+
VI-
Grounding
*1 Use 2-core shielded twisted pair cable for the analog output lines, and
separate the analog output lines from other power lines or inductive lines.
*2 The grounding resistance should be 100 Ω or less.
3.3 Grounding
Grounding should be performed as stated below.
• The grounding resistance should be 100 Ω or less.
• Independent grounding should be performed for best results.
When independent grounding is not performed, perform "shared grounding" of
the following figure.
For details, refer to the following manual.
→ FX
Series User's Manual - Hardware Edition
3S
→ FX
3G
Series User's Manual - Hardware Edition
Other
Other
PLC
PLC
PLC
equipment
equipment
Independent grounding
Shared grounding
Common grounding
(Best condition)
(Good condition)
(Not allowed)
2
• The grounding wire size should be AWG 22-20 (0.3-0.5 mm
).
• The grounding point should be close to the PLC, and all grounding wire should
be as short as possible.
4. Specifications
STARTUP AND
MAINTENANCE
PRECAUTIONS
• Do not disassemble or modify the PLC.
Doing so may cause fire, equipment failures, or malfunctions.
* For repair, contact your local Mitsubishi Electric representative.
• Do not drop the product or exert strong impact to it.
Doing so may cause damage.
DISPOSAL
PRECAUTIONS
• Please contact a certified electronic waste disposal company for the
environmentally safe recycling and disposal of your device.
TRANSPORTATION AND
STORAGE PRECAUTIONS
• The product is a precision instrument. During transportation, avoid impacts
larger than those specified in the general specifications by using dedicated
packaging boxes and shock-absorbing palettes.
Failure to do so may cause failures in the product.
After transportation, verify operation of the product and check for damage of
the mounting part, etc.
4.1 Applicable PLC
Model name
Applicability
FX
Series PLC
Ver. 1.00 or later (from first production)
3S
FX
Series PLC
Ver. 1.10 or later
3G
The version number can be checked by monitoring D8001/D8101 as the last three
digits indicate it.
• The number of connectable expansion boards varies depending on the main
unit as follows:
FX
, FX
-14M , FX
-24M
Main units: 1 unit
3S
3G
3G
FX
-40M , FX
-60M
Main units: 2 units
3G
3G
Never stack up two or more expansion boards.
For details on the system configuration, refer to the following manual.
→ FX
/FX
/FX
/FX
/FX
Series User's Manual
3S
3G
3GC
3U
3UC
- Analog Control Edition
4.2 General Specifications
The general specifications are equivalent to the PLC main unit.
For general specifications, refer to the following manuals.
→ FX
Series User's Manual - Hardware Edition
3S
→ FX
3G
Series User's Manual - Hardware Edition
4.3 Performance Specifications
Specifications
Item
Voltage output
0 to 10 V DC
Analog output
(External load resistance:
range
2 kΩ to 1 MΩ)
Digital input
12 bits, binary
Resolution
2.5 mV (10 V/4000)
• ±0.5 % (±50 mV) for full
scale of 10 V(when ambient
temperature is 25 °C±5 °C)
• ±1.0 % (±100 mV) for full
scale of 10 V
(when ambient temperature
is 0 °C to 55 °C)
Shipment adjustment is carried
out by external load resistance
Total accuracy
2 kΩ.
If ex t er n al l o ad re s i s ta nc e
becomes larger than 2 kΩ, the
output voltage will increase
slightly.
When the load is 1 MΩ, the
output voltage becomes about
2 % higher than the correct
value.
D/A
60 μs
Other
conversion
equipment
(The data will be updated at every scan time of the PLC.)
time
0 to 4000 are adjusted to 0 to
10 V when the external load
resistance is 2 kΩ.
10V
output
characteristics
0
4000
4080
Digital input
Caution:
An area of dead band is located
in the region of 0 V.
Therefore the output analog
value may not represent the
digital value accurately.
Insulation
No insulation between the PLC.
method
Occupied
0 point (This number is not related to the maximum number of
points
input/output points of the PLC.)
4.4 List of Special Devices
Device number
FX
3G
FX
3S
Board A Board B
Switches the output mode
M8260 M8260 M8270
OFF: Voltage output ON: Current output
Output Holding Function Cancellation
Special
Setting
auxiliary
OFF: Holds the analog data output just
relay
M8264 M8264 M8274
before stop of the PLC.
ON: Output the offset data at stop of
the PLC.
D8260
D8260
D8270 Output setting data
Error status
b0: Output data setting error
Special
b1: Unused
data
D8268
D8268
D8278
b2: Unused
register
b3: Unused
b4: EEPROM error
b15 to b5: Unused
D8269
D8269
D8279 Model code = 4
As for the details of the special devices, refer to the following manual.
→ FX
3S
/FX
3G
/FX
3GC
/FX
3U
/FX
3UC
Series User's Manual - Analog Control Edition
「电器电子产品有害物质限制使用标识要求」的表示方式
Note: This symbol mark is for China only.
含有有害6物质的名称, 含有量, 含有部品
Current output
本产品中所含有的有害6 物质的名称, 含有量, 含有部品如下表所示。
 
4 to 20 mA DC
(External load resistance:
500 Ω or less)
产品中有害物质的名称及含量
11 bits, binary
8 μA (16 mA/2000)
部件名称
(Pb)
外壳
可编程
控制器
• ±0.5 % (±80 μA) for full scale
印刷基板
×
of 16 mA (when ambient
temperature is 25 °C±5 °C)
本表格依据SJ/T 11364的规定编制。
• ±1.0 % (±160 μA) for full
scale of 16 mA
○:表示该有害物质在该部件所有均质材料中的含量均在GB/T 26572
(when ambient temperature
规定的限量要求以下。
is 0 °C to 55 °C)
×:表示该有害物质至少在该部件的某一均质材料中的含量超出GB/T
26572规定的限量要求。
基于中国标准法的参考规格:GB/T15969.2
0 to 2000 are adjusted to 4 to
20 mA when the external load
resistance is 250 Ω.
20mA
4mA
0
2000
2040
Digital input
R: Read W: Write
Description
R/W
R/W
R/W
R/W
R/W
R
有害物质
多溴
六价铬
多溴联苯
二苯醚
(Hg)
(Cd)
(Cr(VI))
(PBB)
(PBDE)
This manual confers no industrial property rights or any rights of any other kind,
nor does it confer any patent licenses. Mitsubishi Electric Corporation cannot be
held responsible for any problems involving industrial property rights which may
occur as a result of using the contents noted in this manual.
Warranty
Exclusion of loss in opportunity and secondary loss from warranty liability
Regardless of the gratis warranty term, Mitsubishi shall not be liable for compensation to:
(1) Damages caused by any cause found not to be the responsibility of Mitsubishi.
(2) Loss in opportunity, lost profits incurred to the user by Failures of Mitsubishi products.
(3) Special damages and secondary damages whether foreseeable or not, compensation for
accidents, and compensation for damages to products other than Mitsubishi products.
(4) Replacement by the user, maintenance of on-site equipment, start-up test run
and other tasks.
This product has been manufactured as a general-purpose part for general
industries, and has not been designed or manufactured to be incorporated in
a device or system used in purposes related to human life.
Before using the product for special purposes such as nuclear power, electric
power, aerospace, medicine or passenger movement vehicles, consult with
Mitsubishi Electric.
This product has been manufactured under strict quality control. However