SMC Networks HECR Series Installation And Maintenance Manual

SMC Networks HECR Series Installation And Maintenance Manual

Water cooled thermo con for rack mount
Hide thumbs Also See for HECR Series:

Advertisement

Quick Links

HEC-OM-U015
First edition : 2017. Oct
Installation and Maintenance Manual
Water Cooled Thermo Con for Rack Mount
HECR Series
Original Instructions
1 Read Before Using
Thank you for purchasing SMC's Thermo-con (hereinafter referred to as
the "product"). This "Installation and Maintenance Manual" (hereinafter
referred to as "this manual") briefly explains the essential safety instruction
procedures to start and stop the product and reset its alarms. Read this
manual before using.
2 Safety Instructions
This manual contains essential information for the protection of users and
others from possible injury and/or equipment damage.
 Read this manual before using the product, to ensure correct handling,
and read the manuals of related apparatus before use.
 Keep this manual in a safe place for future reference.
 These instructions indicate the level of potential hazard by label of
"Caution", "Warning" or "Danger", followed by important safety
information which must be carefully followed.
 To ensure safety of personnel and equipment the safety instructions in
this manual and the product catalogue must be observed, along with
other relevant safety practices.
If instructions are not followed there is a
Caution
possibility of injury or equipment damage.
If instructions are not followed there is a
Warning
possibility of serious injury or loss of life.
In extreme conditions, there is a possibility of
Danger
serious injury or loss of life.
 This manual provides the following symbols in addition to "Danger",
"Warning", and "Caution" to present warning details in an easy-to-
understand manner.
This symbol warns you of potential electrical shock.
This symbol warns you of potential burns.
 During operation or maintenance of the product, do not disable the
interlock function of any device. Otherwise unexpected personnel injury
or damage to the product may occur.
 When turning on/off the power observe the procedure. Otherwise
unexpected malfunction or danger may occur.
 When maintaining, cleaning or in case of emergency, turn off the power
source.
 After identifying a problem be sure to check the cause and take
necessary countermeasures before turning on the power.
 The product is operated at high voltage.
 The compatibility of equipment is the responsibility of the person
who designs the system or decides its specifications.
Since the products specified here can be used in various operating
conditions, their compatibility with the specific system must be based on
specifications or after analysis and/or tests to meet specific requirements.
 Only trained personnel should handle or operate the product.
Transportation, installation and maintenance of the product can be
dangerous and should be done by persons who have full knowledge and
experience on the product and system. Cover panels of the product should
be opened only by qualified service technicians or qualified personnel.
 Do not modify or reconstruct the unit.
 Read all warning and caution labels carefully and keep them in mind.
Do not peel off or rub alert warning and caution labels. Confirm locations
of alert warning and caution labels.
 Do not service machinery/equipment or attempt to remove
components until safety is confirmed.
2 Safety Instructions Continued
1) Inspection and maintenance of machinery/equipment should only be
performed after confirmation of safe locked-out positions.
2) When equipment is to be removed, confirm the safety process as
mentioned above. Switch off electrical supplies and ensure any high
temperature parts have cooled to ambient temperature.
3) Before machinery/equipment is re-started, ensure all safety measures
are taken so the product and system can be started in a safe manner.
4) Do not use this product outdoor (indoor use).
 Do not use this product outside of the specifications. Contact SMC
if it is to be used in any of the following conditions.
1) Conditions and environments beyond the given specifications.
2) Installations in conjunction with atomic energy, railway, air navigation,
vehicles, medical equipment, food and beverage, recreation equipment,
emergency stop circuits, press applications, or safety equipment.
 If abnormal conditions occur, such as abnormal noise or smoke, or water
leakage, take the following actions。
1) Shut down power.
2) Contact an authorised SMC dealer for repair.
 After shutting down the power supply, ensure a time interval at least
3sec between ON and OFF. Restarting the product within that interval
may cause it to malfunction.
 Do not use devices that generate electromagnetic radiation such as
cellular phones near the product. There is a possibility that this can
cause the product to malfunction.
 This unit has several interlock functions, which activate when a dangerous
operation or condition occurs to stop the product and make it safe. This is
a function to protect personnel and restrict operation that may cause
damage to the product or facility, and to remove dangers related to safety.
 When dispose the product, contact an industrial waste disposal
company for disposal of the product. To minimize the risk, drain the fluid
from the product when it is scrapped. If the fluid is left inside, an accident
and damage can result during transportation.
3 Specifications
3.1 General Description and Intended Use
This product uses a built in pump to circulate liquid (water or 20% EG) at a
constant temperature, controlled by Thermo-Electric (Peltier) Modules. This
circulating fluid cools parts of the customer's machine that generates heat.
3.2 General Specifications
Item
Spec.
Model No.
HECR008-W
HECR012-W
10.0 to 60.0 C (No dew condensation)
Operation temp. range
-9.9 to 80.0 C
Indication temp. range
Temp: 10 to 35 C
Humidity : 35 to 80%RH
Ambient environment
Altitude : up to 1000m
Environment : No corrosive gas, solvent such as thinner and flammable gas
Temp :-40 to 70 C (No dew condensation and icing)
Storage environment
Humidity : 5 to 95%RH
Environment : No corrosive gas, solvent such as thinner and flammable gas
Indication accuracy: +/- 0.2 C.
Temperature drift: +/- 0.2C
Accuracy related to temp
Stability: +/- 0.01 to 0.03 C
(Circulating fluid OUT is directly connected with IN)
Cooling capacity
Approx. 800W
Approx. 1200W
(Set Temp. 20C and Facility
(Circulating fluid flow rate 3L/min)
(Circulating fluid flow rate 3L/min)
water Temp. 20C, 10L/min)
Circulating fluid
Water, Ethylene glycol solution up to 20%
Tank capacity
Approx.1.3L
Pump capacity
Refer to performance chart.
Port size
IN/OUT: Rc3/8 , Drain: CPC PLCD16004
Wetted materials
Stainless steel, EPDM, NBR, Ceramic, PPE, PPS, Carbon, Polyethylene, POM
Required flow rate
10 to 15 L/min
10 to 35 C
Temperature range
Pressure range
0.5 MPa or less
Port size
IN/OUT: Rc3/8
Wetted materials
SUS304
Single phase AC100 to 240V(+/- 10%),
Single phase AC200 to 240V(+/- 10%),
Power supply
50/60Hz
50/60Hz
Max.10A(100V)
Max.7A (200V)
Current consumption
Max.4A(240V)
Max.6A (240V)
Inrush current
50A or less
14A
Over current protection
circuit protector
Voltage interruptions
20ms or less
Insulation resistance
50M or more (DC500V)
Over voltage category
Category II
Pollution degree
Pollution degree II
Limitation of hazardous
RoHS compliant products
substance
3 Specifications Continued
Item
Spec.
Model No.
HECR008-W
HECR012-W
Acoustic noise
48dBA
Cooling method
Water cooled
Auto tuning, Off set function, Learning control function, External tuning control function,
Main functions
Temperature sensor fine control function, Setting value memory function, Upper / lower
temperature limit alarm function, Output shut off alarm, Communication,
Membrane key sheet
LCD display panel (with back light)
Input operation and
Output shut off alarm,
indications
Upper / lower temperature limit alarm : Relay contact specification
DC30V, 2A (Resistance load)
DC30V, 1A (Induction load)
RS-232C / RS-485
Communications:
Setting of target temperature, Reading of the value detected by temperature sensor,
Reading of warning status, Setting and of off-set value, Setting and reading of control
Communications
operation, Setting and reading of PID values, Reading of output ratio.
For operation by communication, it is necessary to order
"Communication Manual".
Use shielded cable for serial communications.
Resistance thermometer sensor (Pt100, 3-wire, class A, 1mA)
Temp. sensor
(Both internal sensor and external sensor)
Painting color
Urban white
Mass (at dry)
Approx 20kg
Approx 21kg
With flow switch: Low flow rate alarm occurs at less than 0.7L/min
NPT fitting: Fluid IN/OUT fittings
Option
With foot and no rack bracket
High head pump
Thermo-con 1pc
Contents of package
Installation and Maintenance Manual 1pc
Power supply connector 1pc
3.3 Performance Charts
Values on the performance charts are not guaranteed values but
representative values. Allow margins for safety when selecting the model.
3.3.1 Cooling Capacity
HECR008-W
Circulating f luid:Water
Circulating f luid:Ethylene glycol 20%
Circulating f luid f low rate:3L/min
Circulating f luid f low rate:3L/min
2500
2500
Facility water f low rate:10L/min
Facility water f low rate:10L/min
2000
Facility water temp. 10deg.C
2000
Facility water temp. 20deg.C
Facility water temp. 20deg.C
1500
1500
1000
1000
500
Facility water temp. 35deg.C
500
0
0
0
10
20
30
40
50
60
70
0
10
20
30
40
Circulating f luid temp. deg.C
Circulating f luid temp. deg.C
*Cooling capacity decrease about 50W when high head pump option selected.
HECR012-W
Circulating f luid:Water
Circulating f luid:Ethylene glycol 20%
Circulating f luid f low rate:3L/min
3000
Circulating f luid f low rate:3L/min
3000
Facility water f low rate:10L/min
Facility water f low rate:10L/min
2500
2500
Facility water temp. 10deg.C
Facility water temp. 20deg.C
2000
2000
1500
1500
1000
1000
Facility water temp. 20deg.C
500
500
Facility water temp. 35deg.C
0
0
0
10
20
30
40
50
60
70
0
10
20
30
40
Circulating f luid temp. deg.C
Circulating f luid temp. deg.C
*Cooling capacity decrease about 50W when high head pump option selected.
3.3.2 Heating Capacity
HECR008-W
Circulating f luid:Water
Circulating f luid:Ethylene glycol 20%
Circulating f luid f low rate:3L/min
2500
Circulating f luid f low rate:3L/min
2500
Facility water f low rate:10L/min
Facility water f low rate:10L/min
2000
2000
Facility water temp. 35deg.C
Facility water temp. 20deg.C
1500
1500
1000
1000
Facility water temp. 20deg.C
500
500
Facility water temp. 10deg.C
0
0
0
10
20
30
40
50
60
70
0
10
20
30
40
Circulating f luid temp. deg.C
Circulating f luid temp. deg.C
3 Specifications Continued
HECR012-W
Circulating f luid:Water
Circulating f luid f low rate:3L/min
3000
3000
Facility water f low rate:10L/min
Facility water temp. 35deg.C
2500
2500
2000
2000
1500
1500
1000
1000
Facility water temp. 20deg.C
500
500
Facility water temp. 10deg.C
0
0
0
10
20
30
40
50
60
70
Circulating f luid temp. deg.C
3.3.3 Pump Capacity
HECR008/012-W
0.18
0.35
0.16
Water
0.30
0.14
0.25
0.12
Ethylene glycol 20%
0.20
0.10
0.08
0.15
0.06
0.10
0.04
0.05
0.02
0.00
0.00
0.0
1.0
2.0
3.0
4.0
5.0
Circulating f luid f low rate L/min
Normal
3.3.4 Pressure Loss in Facility Water Circuit
HECR008-W
HECR012-W
0.10
0.10
0.08
0.08
0.06
0.06
0.04
0.04
0.02
0.02
0.00
0.00
0
5
10
15
20
Facility water f low rate L/min
3.4 Connector Specifications
Description
No.
Signal
HECR008-W
HECR012-W
Power supply
N
AC100 to 240V
AC200 to 240V
connector
L
AC100 to 240V
AC200 to 240V
(IEC60320,C14)
E
PE
RS-232C
RS-485
1
Unused
BUS +
Communication
2
RXD (RD)
Unused
connector
50
60
70
3
TXD (SD)
Unused
Note: Always
use shielded
4
Unused
Unused
cable connected
5
SG
to this connector.
6-8
Unused
Unused
9
Unused
BUS -
1-2
Unused
3-5
PT-RTD
Output Cutoff Alarm a contact
6
(OPEN During Alarm)
Signal・
7
Output Cutoff Alarm Common
External
temperature
Output Cutoff Alarm b contact
8
sensor
(CLOSE During Alarm)
connector
Temperature Alarm a contact
Note: Always
9
(OPEN During Alarm)
50
60
70
use shielded
10
Temperature Alarm Common
cable connected
to this connector.
Temperature Alarm b contact
11
(CLOSE During Alarm)
12-14
Unused
15
FG
50
60
70
Circulating f luid:Ethylene glycol 20%
Circulating f luid f low rate:3L/min
Facility water f low rate:10L/min
Facility water temp. 20deg.C
0
10
20
30
40
50
60
70
Circulating f luid temp. deg.C
Water
Ethylene glycol 20%
0.0
1.0
2.0
3.0
4.0
5.0
6.0
7.0
Circulating f luid f low rate L/min
When high head pump option selected
0
5
10
15
20
Facility water f low rate L/min
Style and Part No.
N
L
E
5 4 3 2 1
9 8 7 6
SG
D-sub 9 pin (socket type)
Fixed screw: M2.6
8
1
15
9
D-sub 15 pin (Socket type)
Fixed screw: M2.6

Advertisement

loading

Summary of Contents for SMC Networks HECR Series

  • Page 1 3) Before machinery/equipment is re-started, ensure all safety measures 2000 2000 HECR Series are taken so the product and system can be started in a safe manner. Auto tuning, Off set function, Learning control function, External tuning control function, 1500...
  • Page 2 3 Specifications Continued 4 Special Features Continued 5 Installation Continued 5 Installation Continued  Offset function  Leakage from the product may damage peripheral equipment. Install a 3.5 Model number of product 1) Strip the sheath from both ends of the cable. This function controls the temperature slide by an offset value from set drain pan under the product to capture leakage.
  • Page 3 5 Installation Continued 6 Operation Continued 6 Operation Continued 9 Maintenance 6.3.1 Level 1-Settings 9.1 Daily Check Modes Setting contents Setting range Default Setting range  Never touch the power switch with wet hands to avoid electrical shock. Sets the unit No. used. This is 1) Indication of display panel: Check temperature condition and confirm Modes Setting contents...
  • Page 4 10 Troubleshooting Continued Operation Reason for alarm Code Description Cause / Measure status setting Internal temp. sensor Check the set value for high value exceeds the high temp. cutoff temperature and temp. cutoff confirm the temperature really temperature. reaches this value. Internal temp.