Toshiba RAV-GM561ATP-E Service Manual page 59

Outdoor unit, digital inverter
Hide thumbs Also See for RAV-GM561ATP-E:
Table of Contents

Advertisement

Error mode detected by remote controller or central controller (TCC-LINK)
Check code
No communication with master indoor unit
Not displayed at all
(Operation on
Remote controller wiring is not correct.
remote controller
Power of indoor unit is not turned on.
cannot be operated.)
Automatic address cannot be completed.
No communication with master indoor unit
E01
Disconnection of inter-unit wire between
remote controller and master indoor unit
∗1
(Detected by remote controller side)
Signal send error to indoor unit
E02
(Detected by remote controller side)
There are multiple main remote controllers.
E09
(Detected by remote controller side)
L20
Duplicated indoor central addresses on
communication of central control system
Central controller
(Detected by indoor/central controller side)
L20
∗2
Communication circuit error of central
Central controller
control system
(Send)
(Detected by central controller side)
C05
(Receive)
C06
Indoor Gr sub unit error
(Detected by central controller side)
Central controller
P30
∗1 The check code cannot be displayed by the wired remote controller.
(Usual operation of air conditioner becomes unavailable.)
For the wireless models, an error is notified by indication lamp.
∗2 This trouble is related to communication of remote controller (A, B), central system (TCC-LINK U3, U4),
and [E01], [E02], [E03], [E09] or [E18] is displayed or no check display on the remote controller according
to the contents.
Operation of diagnostic function
Cause of errors
(Automatically reset)
∗ If center exists,
(Automatically reset)
∗ If center exists,
continues operation.)
(Automatically reset)
(By remote controller)
Status of
Condition
air conditioner
Stop
Stop
Displayed when
error is detected
operation continues.
Stop
Displayed when
error is detected
operation continues.
Stop
Displayed when
(Sub unit
error is detected
Stop
Displayed when
error is detected
Continues
Displayed when
error is detected
Continuation/Stop
Displayed when
(According
error is detected
to each case)
- 59 -
FILE NO. SVM-18043
Judgment and measures
Power supply error of remote controller, Indoor
EEPROM error
1. Check remote controller inter-unit wiring.
2. Check remote controller.
3. Check indoor power wiring.
4. Check indoor P .C. board.
5. Check indoor EEPROM.
(including socket insertion)
→ Automatic address repeating phenom-
enon generates.
Receiving error from remote controller
1. Check remote controller inter-unit wiring.
2. Check remote controller.
3. Check indoor power wiring.
4. Check indoor P .C. board.
Error sending of remote controller
1. Check sending circuit inside the remote
controller.
→ Replace remote controller.
1. In 2-remote controllers (including wireless),
there are multiple main units.
Check that there are 1 main remote
controller and other sub remote controllers.
1. Check setting of central control system
network address. (Network adapter SW01)
2. Check network adapter P .C. board.
1. Check communication wire / miswiring
2. Check communication (U3, U4 terminals)
3. Check network adapter P .C. board.
4. Check central controller (such as central
control remote controller, etc.)
5. Check terminal resistance. (TCC-LINK)
Check the check code of the corresponding
unit from remote controller.