External Electronic Expansion Valve Kit (Atk-Svrk56Ba); Flare Insulator - Sanyo ECO R410A Installation Instructions Manual

Eco-i system air conditioner
Table of Contents

Advertisement

3-24. External Electronic Expansion Valve Kit (ATK-SVRK56BA)

Precautions in this manual are given in the form of "Warnings" or "Cautions." Both types of precautions contain
important information related to your safety, the safety of users, and the correct operation, installation,
or maintenance of the air conditioning system. Be sure to carefully observe all relevant precautions.
This symbol refers to a hazard or unsafe practice which can result in severe personal injury
WARNING
or death.
This symbol refers to a hazard or unsafe practice which can result in personal injury or product
CAUTION
or property damage.
• This external electronic expansion valve is compatible with the refrigerants listed below.
R410A, R407C, R22
1. Checking Parts
Please check these parts below that came in the box.
Description
External electronic
1
expansion valve
(Extension cord 26.2 ft.)
2

Flare insulator

2. Positioning for Installation
• The valve should be connected to the liquid tube. Determine the position for installation referring to the diagram of
outer dimensions. (Fig. 3-52) Refrigerant-flow noise may occur from the external electronic expansion valve. As a
guide, the distance from the indoor unit should be a minimum of 16.4 feet, but less than 26.2 feet. (Install away from
locations where strictly quiet operation is required.)
If this distance is unavailable, install inside the ceiling or in another location where noise insulation is possible.
This is a functional component, and therefore may require inspection and replacement. Consider this when deciding
the installation location. (For example, place near an inspection port, or provide one.)
• This valve is for indoor use. Do not install the valve outdoors.
Diagram of outer dimensions
Indoor
side
Connecting portion B
Shape
Q'ty
Connecting portion B
Extension cord (26.2 ft.)
(10-53/64)
A
Description
Clamp
3
(Large: 13-25/32",
Small: 7-7/8")
1
4
Installation manual
2
5
Insulating tape
Outdoor
side
Type
A
B
Fig. 3-52
24
Shape
White
(heat resisting)
56
160
12-51/64
14-11/64
o 1/4
o 3/8
Unit: in.
Q'ty
Large: 2
Small: 4
1
2