9-2. Air conditioner does not operate.

9-2-1. Circuit breaker trips (or fuse blows).
A. When the circuit breaker is set to ON, it is tripped soon. (Resetting is not possible.)
There is a possibility of ground fault.
Check insulation resistance.
If resistance value is 2M½ or less, insulation is defective ("NO").
WARNING
*
Set circuit breaker to OFF.
1 Remove both power supply wires
and inter-unit wires from terminal
plate in outdoor unit.
Measure insulation resistance
of outdoor unit.
2 Remove inter-unit wires from
terminal plate in indoor unit.
Measure insulation resistance
of indoor unit.
2
1
Indoor
Outdoor
Inter–unit
unit
unit
wiring
1
1
8
2
2
7
3
3
4
4
5
5
6
6
G
G
G
NO
NO
55
1
Power supply
wiring
L2
Power
Circuit
L1
supply
breaker
Ground
Insulation of
outdoor unit
is defective.
Measure insulation
resistance of electrical
parts in outdoor unit.
Insulation of
indoor unit
is defective.
Measure insulation
resistance of electrical
parts in indoor unit.