Air Conditioner Does Not Operate - Sanyo SAP-K181AA Technical & Service Manual

Split system air conditioner
Table of Contents

Advertisement

9-2. Air conditioner does not operate.

9-2-1. Circuit breaker trips (or fuse blows).
A. When the circuit breaker is set to ON, it is tripped soon. (Resetting is not possible.)
There is a possibility of ground fault.
Check insulation resistance.
If resistance value is 2MΩ or less, insulation is defective ("NO").
Indoor
unit
1
2
4
5
WARNING
*
Set circuit breaker to OFF.
1 Remove both power supply wires
and inter-unit wires from terminal
plate in outdoor unit.
Measure insulation resistance
of outdoor unit.
2 Remove inter-unit wires from
terminal plate in indoor unit.
Measure insulation resistance
of indoor unit.
B. Circuit breaker trips in several minutes after turning the air conditioner on.
There is a possibility of short circuit.
Check capacity of circuit breaker.
Capacity of circuit breaker is
suitable.
Measure resistance of outdoor fan
motor winding.
Measure resistance of compressor
motor winding.
Inter-unit
Outdoor
power wiring
unit
2
1
1
2
4
5
NO
1
Circuit
breaker
Ground
NO
NO
Replace with suitable
one (larger capacity).
29
Power
supply
Insulation of
outdoor unit
is defective.
Measure insulation
resistance of electrical
parts in outdoor unit.
Insulation of
indoor unit
is defective.
Measure insulation
resistance of electrical
parts in indoor unit.

Advertisement

Table of Contents
loading

Table of Contents