Electrical Wiring; General Precautions On Wiring; Recommended Wire Length And Wire Diameter For Power Supply System - Sanyo 85464359982001 Installation Instructions Manual

W-2way system air conditioner
Table of Contents

Advertisement

07-007 W-2WAY_II_NA
1/23/07

5. ELECTRICAL WIRING

5-1. General Precautions on Wiring

(1) Before wiring, confirm the rated voltage of the unit as
shown on its nameplate, then carry out the wiring
closely following the wiring diagram.
(2) Provide a power outlet to be used exclusively for each
unit, and a power supply disconnect and circuit breaker
for overcurrent protection should be provided in the
exclusive line.
(3) To prevent possible hazards from insulation failure, the
unit must be grounded.
(4) Each wiring connection must be done in accordance
with the wiring system diagram. Wrong wiring may
cause the unit to misoperate or become damaged.
(5) Do not allow wiring to touch the refrigerant tubing,
compressor, or any moving parts of the fan.
(6) Unauthorized changes in the internal wiring can be very
dangerous. The manufacturer will accept no
responsibility for any damage or misoperation that
occurs as a result of such unauthorized changes.

5-2. Recommended Wire Length and Wire Diameter for Power Supply System

Outdoor unit
Type
CHDX09053
CHDX14053
Indoor unit
Type
K
A, X, T, U
D
Control wiring
(C) Inter-unit (between outdoor and
indoor units) control wiring
AWG #18 (0.75 mm
Use shielded wiring*
Max. 3,280 ft.
NOTE
* With ring-type wire terminal.
6:09 PM
Page 59
(A) Power supply
Time delay fuse or
circuit capacity
Wire size Max. length
AWG #8
64 ft.
AWG #4
100 ft.
(B) Power supply
Time delay fuse or
circuit capacity
AWG #14
Max. 492 ft.
15 A
Max. 426 ft.
15 A
Max. 196 ft.
15 A
(D) Remote control wiring
2
)
AWG #18 (0.75 mm
Use shielded wiring
Max. 1,640 ft.
(7) Regulations on wire diameters differ from locality to
locality. For field wiring rules, please refer to your
LOCAL ELECTRICAL CODES before beginning.
You must ensure that installation complies with all
relevant rules and regulations.
(8) To prevent malfunction of the air conditioner caused by
electrical noise, care must be taken when wiring as
follows:
G The remote control wiring and the inter-unit control wiring
should be wired apart from the inter-unit power wiring.
G Use shielded wires for inter-unit control wiring between
units and ground the shield on both sides.
(9) If the power supply cord of this appliance is damaged, it
must be replaced by a repair shop appointed by the
manufacturer, because special purpose tools are
required.
60 A
80 A
(E) Control wiring for group control
2
)
AWG #18 (0.75 mm
Use shielded wiring
Max. 1,640 ft. (Total)
(F) Inter-outdoor unit control wiring
AWG #18 (0.75 mm
Use shielded wiring
59
2
)
2
)
Max. 1,640 ft.