3-6. How to Install the Ceiling Panel

3-6-1. Before Installing the Ceiling Panel
Checking the unit position
(1) Check that the ceiling hole is within this range:
33-55/64 × 33-55/64 to 35-53/64 × 35-53/64 in.
(2) Use the full-scale installation diagram (from the
packaging) that was supplied with the unit to
determine the positioning of the unit on the ceiling
surface. If the positions of the ceiling surface and
unit do not match, air leakage, water leakage, flap
operation failure, or other problems may result.
CAUTION
G
Never place the panel face-down. Either hang
it vertically or place it on top of a projecting
object. Placing it face-down will damage the
surface.
G
Do not touch the flap or apply force to it.
(This may cause flap malfunction.)
Remove the air-intake grille and air filter from the
ceiling panel. (Figs. 3-16, 3-17 and 3-18)
a) Remove the 2 screws on the latch of the air-intake
grille. (Fig. 3-16)
b) Slide the air-intake grille catches in the direction
shown by the arrows
(Fig. 3-17)
c) With the air-intake grille opened, remove the grille
hinge from the ceiling panel by sliding it in the direc-
tion shown by the arrow
Removing the corner cover
a) Slide the corner cover to the direction shown
by the arrow
1
(Fig. 3-18).
Corner cover
6:09 PM
Page 27
1
to open the grille.
2
. (Fig. 3-18)
to remove the corner cover.
Push
A
must be within the range of 15/32 – 43/64 in.
If not within this range, malfunction or other trouble may result.
A
Ceiling side
Air-intake grille
Ceiling panel
1
1
Air-intake grille hinge
Fig. 3-16
Corner cover
1
Strap
Fig. 3-18
27
Main unit
Ceiling opening
dimension
Fig. 3-13
Flap
Fig. 3-14
Screw
Latch
Fig. 3-15
2
Fig. 3-17
Ceiling panel
X