1MRS758734
5.10.
COM600 series 5.1
Substation Analytics Technical Manual

Signals

Table 5.10-1 SSCBR input signals
Name
Type
R_IL1
DOUBLE
R_IL2
DOUBLE
R_IL3
DOUBLE
CB_POS
INT
R_GAS_PRES
BOOLEAN
R_SPRING_CHARG
BOOLEAN
R_INACT_DAYS
INT
R_NUM_CB_OPR
INT
Table 5.10-2 SSCBR Output Signals
Name
Type
TrvTOpAlm
BOOLEAN
TrvClAlm
BOOLEAN
CbOprAlm
BOOLEAN
CBLifeAlarm
BOOLEAN
InActAlm
BOOLEAN
CBAccEneAlarm
BOOLEAN
SprChrAlm
BOOLEAN
PresAlam
BOOLEAN
TrvOpnTm
DOUBLE
TrvClTm
DOUBLE
CBAccEnePhsA
DOUBLE
Default
Description
0
Phase A Current
0
Phase B Current
0
Phase C Current
0
Signal for open posi-
tion of apparatus from
I/O
0
Gas Pressure
0
Spring charge
0
Inactive days
0
Number of CB opera-
tion
Default
Description
0
CB open travel time
exceeded set value
0
CB close travel time
exceeded set value
0
Number of CB opera-
tions exceeds alarm
limit
0
Remaining life of CB
exceeded alarm limit
0
Inactive days
exceeded set value
0
Accumulated currents
power (I
alarm limit
0
Spring charging time
has crossed the set
value
0
Pressure below alarm
level
0 = false
CB Open travel time
0 = false
CB Close travel time
0 = false
Phase A accumulated
energy
y
t),exceeded