ABB COM600 series User's & Technical Manual page 51

5.1 substation analytics
Hide thumbs Also See for COM600 series:
Table of Contents

Advertisement

1MRS758734
COM600 series 5.1
Substation Analytics Technical Manual
functional_module_diagram_for_circuit_breaker_gas_pressure_alarm.png
Figure 5.6-1 Functional module diagram for calculating accumulative energy and alarm
Accumulated energy calculator
This module calculates the accumulated energy I
y
t [(kA)
y
s]. The factor y is set with the
Current exponent setting.
The calculation is initiated with the POSCLOSE input opening events. It ends when the
RMS current becomes lower than the Acc stop current setting value.
significance_of_the_difference_cor_time_setting.png
Figure 5.6-2 Significance of the Difference Cor time setting
The Difference Cor time setting is used instead of the auxiliary contact to accumulate
the energy from the time the main contact opens. If the setting is positive, the calculation
of energy starts after the auxiliary contact has opened and when the delay is equal to the
value set with the Difference Cor time setting. When the setting is negative, the calculation
starts in advance by the correction time before the auxiliary contact opens.
The accumulated energy outputs IPOW_A (_B, _C) are available in the monitored data
view on the LHMI or through tools via communications. The values can be reset by
setting the parameter CB accum. currents power setting to true in the clear menu from
WHMI or LHMI. The set values will be taken into use when trigger application is next
time run.
Alarm limit check
The IPOW_ALM alarm is activated when the accumulated energy exceeds the value set
with the Alm Acc currents Pwr threshold setting. However, when the energy exceeds
51