Output charts
Type
Fan
Airflow
position
[m
AR3210CW max
1500
min
1000
AR3215CW max
2600
min
1700
AR3220CW max
3150
min
2500
Type
Fan
Airflow
position
[m
AR3210CW max
1500
min
1000
AR3215CW max
2600
min
1700
AR3220CW max
3150
min
2500
*
) Recommended outlet air temperature for good comfort and optimized output.
1
*
) Nominal output at given supply and return water temperature.
2
12
Supply water temperature: 60 °C
Room temperature: +18 °C
Outlet air temperature: +35 °C*
Output
Return water
temp.
/h]
[kW]
[°C]
3
8,8
43
5,9
37
15,2
42
10,0
35
18,2
41
14,3
36
Supply water temperature: 55 °C
Room temperature: +18 °C
Outlet air temperature: +35 °C*
Output
Return water
temp.
/h]
[kW]
[°C]
3
8,8
46
5,9
39
15,2
46
10,0
39
18,2
44
14,3
40
AR3200C
Water temperature: 60/40 °C
Room temperature: +18 °C
1
Water
Pressure
Output *
flow
drop
[l/s]
[kPa]
[kW]
0,12
14,0
8,2
0,06
4,0
6,4
0,20
48,5
14,4
0,10
12,5
11,1
0,23
27,5
17,9
0,14
11,2
15,6
Water temperature: 55/35 °C
Room temperature: +18 °C
1
Water
Pressure
Output *
flow
drop
[l/s]
[kPa]
[kW]
0,24
44,9
6,65
0,09
7,51
5,2
0,41
174
11,9
0,15
29,4
9,17
0,40
74,1
14,8
0,23
27,8
12,8
2
Outlet
Water
Pressure
air temp.
flow
drop
[°C]
[l/s]
[kPa]
34
0,10
9,2
37
0,08
5,9
34
0,17
37,2
37
0,13
23,1
35
0,22
24,1
36
0,19
18,6
Outlet
Water
Pressure
2
air temp.
flow
drop
[°C]
[l/s]
[kPa]
31
0,08
6,5
33
0,06
4,1
32
0,14
26,5
34
0,11
16,5
32
0,18
17,1
33
0,15
13,2

Advertisement