Ensure the hold-down bolts on the compressor are secure and have
not vibrated loose during shipment. Check that vibration grom-
mets have been installed. Visually check all piping and clamps. The
entire refrigeration system has been factory charged and tested,
making it unnecessary to field charge. Factory charges are shown
in Appendix C and on the unit nameplate.
S
-U
P
C
TART
P
ROCEDURE AND
HECKLIST
Begin with power turned off at all disconnects.
1. Turn thermostat system switch to "Cool," and fan switch
to "Auto" and turn temperature setting as high as it will
go.
2. Inspect all registers and set them to the normal open
position.
3. Turn on the electrical supply at the disconnect.
4. Turn the fan switch to the "ON" position. The blower
should operate after a 7-second delay.
5. Turn the fan switch to "Auto" position. The blower should
stop after a 65 second delay.
6. Slowly lower the cooling temperature until first stage COOL
(LOW COOL) starts. The blower, both fans, and first stage
compressor should now be operating. Allow the unit to
run 10 minutes, make sure cool air is being supplied by
the unit.
7. Lower the cooling temperature further until second stage
COOL (HIGH COOL) starts. The blower, both fans, and both
compressors should now be operating. Allow the unit to
run 10 minutes, make sure cool air is being supplied by
the unit.
8. Turn the temperature setting to the highest position,
stopping the unit. The indoor blower will continue to run
for 65 seconds.
9. Turn the thermostat system switch to "OFF" and
disconnect all power when servicing the unit.
S
-
P
C
TART
UP
ROCEDURE AND
HECKLIST FOR
Models with a V in the 11th position of the model number.
For 2 speed models, the indoor blower will operate on low speed
when in "Fan Only" mode or while in first stage "Cooling" mode.
Unit will operate on high speed in "Heating" mode and while in
second stage "Cooling" mode.
The start-up procedure is the same as for "Air Conditioning Start-
up Procedure" with the understanding that in Step 6, the indoor
blower will run at low speed (~1175 motor rpm) and in Step 7, the
indoor blower will operate at high speed (~1775 motor rpm).
2 S
M
:
PEED
ODELS
NOTE: While in the Cooling Mode, to prevent frost from forming
on the evaporator while the unit is operating in outdoor
temperatures of 65°F or lower, it is recommended that a low
ambient kit (LAKT-**) is used. This is strongly recommended for 2
Speed models due to the lower airflow while in the first stage
cooling. To further protect the compressor from damage during
low ambient conditions, a Freezestat Kit (FSK01) can be added that
turns the compressor off when the evaporator temperature drops
too low.
HIGH VOLTAGE!
D
ISCONNECT ALL POWER BEFORE SERVICING OR
. M
INSTALLING THIS UNIT
. F
BE PRESENT
AILURE TO DO SO MAY CAUSE PROPERTY
,
DAMAGE
PERSONAL INJURY OR DEATH
R
P
EFRIGERATION
ERFORMANCE
Check that compressor RLA corresponds to values shown in Ap-
pendix B. RLA draw can be much lower than values listed at low
load conditions and low ambient condensing temperatures. Val-
ues in Appendix B can slightly exceed at high load conditions and
high ambient condensing temperatures.
F
S
C
INAL
YSTEM
HECKS
10. Check to see if all supply and return air grilles are adjusted
and the air distribution system is balanced for the best
compromise between heating and cooling.
11. Check for air leaks in the ductwork. See Sections on Air
Flow Adjustments.
12. Make sure the unit is free of "rattles", and the tubing in
the unit is free from excessive vibration. Also make sure
tubes or lines are not rubbing against each other or sheet
metal surfaces or edges. If so, correct the trouble.
13. Set the thermostat at the appropriate setting for cooling
and heating or automatic change over for normal use.
14. Be sure the Owner is instructed on the unit operation, filter,
servicing, correct thermostat operation, etc.