Automatic start unit for gas/diesel/gasoline generators
with j1939 ecus (62 pages)
Summary of Contents for EMKO EAOM-19
Page 1
- Battery voltage measurement and monitoring - Engine working time monitoring - Simple push-button controlled operation - Two user configurable inputs - Provides charge generator excitation current - Speed sensing from alternator frequency - Fully programmable Instruction Manual. ENG EAOM-19 02 V09 05/17...
Page 2
ABOUT INSTRUCTION MANUAL Instruction manual of EAOM-19 automatic transfer unit consists of two main sections. Explanation of these sections are below. Also, there is other section which include technical specifications of the unit. All titles and page numbers in instruction manual are in “...
3.ELECTRICAL CONNECTIONS......................Page 3.1 TERMINAL LAYOUT AND CONNECTION INSTRUCTIONS............ Page 3.2 ELEKTRICAL CONNECTION DIAGRAM.................. Page 3.2.1 EAOM-19 SINGLE PHASE CONNECTIONS SCHEMATIC FOR TN-C AC POWER SYSTEMS........................Page 3.2.2 EAOM-19 THREE PHASE CONNECTIONS SCHEMATIC FOR TN-C AC POWER SYSTEMS........................Page 3.3 TOP LABEL VIEW OF THE EAOM-19..................
Page 5
EU DECLARATION OF CONFORMITY Manufacturer’s Name : EMKO ELEKTRONIK A.S. Manufacturer’s Address : DOSAB, Karanfil Sk., No:6, 16369 Bursa, TURKEY This declaration is issued under the sole responsibility of the manufacturer. Product Name : Automatic Transfer Unit For Diesel Generators...
1.1 General Specifications The EAOM-19 provides for automatic transfer of a load from mains to generator in the event of a mains failure. The unit is able to detect failure of any phase of the mains and to start and switch over to a generator if the mains voltage goes outside pre-set limits.
1.2 Warranty EMKO Elektronik warrants that the equipment delivered is free from defects in material and workmanship. This warranty is provided for a period of two years. The warranty period starts from the delivery date. This warranty is in force if duty and responsibilities which are determined in warranty document and instruction manual performs by the customer completely.
2.Installation Before beginning installation of this product, please read the instruction manual and warnings below carefully. In package, - One piece unit - Two pieces fixing clamp - One piece instruction manual A visual inspection of this product for possible damage occured during shipment is recommended before installation.
2.4 Environmental Ratings Operating Conditions Operating Temperature -25°C to +70 °C Max. Operating Humidty : 90 Rh (non-condensing) Altitude Up to 2000m. Forbidden Conditions: Corrosive atmosphere Explosive atmosphere Home applications (The unit is only for industrial applications) 2.5 Panel Mounting 1-Before mounting the controller in your panel, make sure that the cut-out is of the right size.
2.6 Installation Fixing Clamp The unit is designed for panel mounting. 1-Insert the unit in the panel cut-out E A O M - 1 from the front. H z . L 1 2 /L L 2 3 /L L 3 1 /L F A IL T O S T A R T...
3.Electrical Connections You must ensure that the unit is correctly configured for your application. Incorrect configuration could result in damage to the process being controlled, and/or personal injury. It is your responsibility, as the installer, to ensure that the configuration is correct. Parameters of the unit has factory default values.
3.2.2 EAOM-19 Three Phase Connections Schematic For TN-C AC Power Systems LOAD MAINS CONTACTOR GENERATOR CONTACTOR GENERATOR MAINS GENERATOR RELAY MAINS RELAY MEASUREMENT MEASUREMENT 5A@250V 5A@250V CIRCUIT CIRCUIT 16A@32V 16A@32V SOLENOID RELAY START CHARGE RELAY GEN. D+(W.L.) STARTER BATTERY NEGATIVE MUST BE GROUNDED Connect the unit as shown in the appropriate diagram, Section 3.2.1 or 3.2.2.
Table 3.1 shows the connections and recommended cable sizes. Table 3.2 describes the functions of the connections. Cable Size Description Notes (mm²) - Battery supply to EAOM-19 Supplies to unit + Battery supply to EAOM-19 Supplies to unit Supplies to Pin + Battery supply input 4,5,6.
TEST position. The red LED shows the EAOM-19 is in the Programming Mode. The LED is lit when the unit is in the Programming Mode, lit lights off when the unit is in the other modes.
Page 20
Number Comment The button is used for changing operating mode of the unit to the TEST Mode. The unit changes operating mode to the TEST Mode and LED (1) is lit when this button is pressed. The LAMP TEST function of the unit is operated and entered in the Programming Mode by using this button.
4.2 Accessing To The Operator Parameters Programming can be carried out only while the unit is in mode. Press the OFF (17) button. If the engine is running, it will stop and the LED (6) lights on. Then proceed as follows: Operation Screen °F °F...
Page 22
The value of parameter P00 °F GEN V. PROG RESET TEST Press Enter button to confirm the Change the parameter changed value or access the value with increment following parameter. and decrement buttons. P01: Mains Voltage Disconnection Level °F GEN V. To exit the User can access to the programming mode,...
4.3 Accessing To The Technician Parameters Programming can be carried out only while the unit is in mode. Press the OFF (17) button. If the engine is running, it will stop and the LED (6) lights on. Then proceed as follows: Operation Screen °F °F...
Page 24
The value of parameter P00 °F GEN V. PROG RESET TEST Press Enter button to confirm the Change the parameter changed value or access the value with increment following parameter. and decrement buttons. P01: Mains Voltage Disconnection Level °F GEN V. To exit the User can access to the programming mode,...
4.5 Explanation of Parameters 4.5.1 Mains Voltage Connection(P00) and Disconnection Level(P01), Upper Limit(P02) P00 Mains voltage connection level P01 Mains voltage disconnection level P02 Mains voltage upper limit In Automatic mode, the unit uses these parameters to decide when to switch the load between the mains supply and the generator.
4.5.2 Alternator Voltage Lower(P03) and Upper Limit(P04), Fault Control Delay(P20) P03 Alternator voltage lower limit P04 Alternator voltage upper limit P20 Alternator voltage fault control delay At the end of Contro on delay time defined by parameter P19, a fault will be reported if the generator voltage goes outside the window defined by the upper and lower limits for more than the time defined as the Alternator voltage fault control delay...
Stop Solenoid 4.5.9 Engine Started Signal (P15) The EAOM-19 must de-energise the Start solenoid, to disconnect the starter motor, once the engine is running. Conversely, if the engine does not start after the pre-set start time, the unit will turn off the starter motor and start again. Hence, the unit must be able to detect when the engine has started.
High Temperature, will be ignored by the EAOM-19. Also, in the event of a mains failure, transfer of the load from mains to generator will be delayed until the end of the Control On Delay period. This period begins when the EAOM-19 has detected engine starting and has cut off the drive to the starter motor.
4.5.16 Oil Sensor Selection ( This parameter determine the function of oil sensor input(Pin 7); 0: Oil level sensor. 1: Oil pressure sensor. If it is selected as oil level sensor(0), the oil pressure parameter (P15.3) of the engine started signals will not be functional. But i f it is selected as oil pressure sensor(1), the oil pressure parameter (P15.3) of the engine started signals will be functional.
5. After a visual inspection to ensure it is safe to proceed, connect the battery supply. 6. On the EAOM-19, press the MAN ENGINE START (14) button. At this moment the LED (3) lights on. 7. Check that the engine start sequence commences. The starter motor should run for the programmed period (P16) for the pre-set (P06) number of times.
2. Check the mains voltage readings on the display. 3. At the EAOM-19, press the AUTO (18) button. The LED (7) on the button should light. 4. Switch off the mains supply to the unit. Check that the generator starts and, after a delay, the load is transferred to the generator.
Page 33
6. Operation 6.1 Alternate Display Description GEN FRQ. BATTERY ALARM GEN V. Four-digit, seven-segment LED display. This multi-function display the selected parameter from the list alongside. Use DISPLAY MODE (23) button to select which parameter is to be displayed, as indicated by the adjacent LEDs. The button selects the parameters in sequence, as follows.
Page 34
Example 1: Using Alternate Display with Single phase selection Mains Voltage L1-N Generator Voltage GEN FRQ. GEN FRQ. °F °F BATTERY BATTERY Press the display ALARM ALARM GEN V. GEN V. mode button. Press the display mode button again. Generator Frequency (Hz) Battery Voltage GEN FRQ.
Page 35
Example 2: Using Alternate Display with Three phase selection Mains Voltage L1-L2 Mains Voltage L1-N GEN FRQ. GEN FRQ. °F °F BATTERY BATTERY Press the display ALARM ALARM GEN V. GEN V. mode button. Press the display mode button again. Mains Voltage L2-L3 Mains Voltage L2-N GEN FRQ.
Page 36
6.2 Failure Indicators Description SPEED Bat.Voltage Failure SPARE 1 SPARE 2 Explanations : (Start Failure LED) : The Unit drives to the starter motor according to values determined in P06 and P16. But, starting the engine is not possible in this values the unit gives a Start Failure.
Page 37
GEN FRQ. °F BATTERY ALARM GEN V. Once the EAOM-19 has given a shutdown signal to the engine it expects the engine to rest. It monitors the Engine Started Signal sources and if they still indicate engine movement when ALARM...
Page 38
6.3 Mode Transition The mode can be changed at any time. Any changes between Auto, Manual and Test modes will not effect the current state of the generator or load connection. 6.4 Manual Start 1. Press the MAN ENGINE START (14) button on the panel the LED (3) will light on. The engine should start.
Page 39
Engine failed to start Check for battery + output at pin 5, (Fuel Solenoid if selected) after Pre-set number Check the signals that the EAOM-19 is using to determine if the of Attempts. engine has started. Refer to engine manual.
Page 40
8. Specifications Equipment Use : Electrical control equipment for generating sets Housing & Mounting : 72mm x 72mm x 95mm. (Including connectors) ¼ DIN43700 plastic housing for panel mounting. Panel Cut-Out : 69mm x 69mm. Protection : NEMA 4X (Ip65 at front panel, Ip20 at rear side). Weight : Approximately 270gr.
Page 41
Display : 4 digits, 7 segments, LED display showin; Mains voltage (Ph-Ph or Ph-N) Alternator voltage (u only) Alternator frequency Battery voltage Engine working time Program parameters Failure Indicators : Start failure LED High temperature LED Low oil pressure LED Over speed LED Generator voltage failure LED Charge generator failure LED...
Page 42
MAINS L1 & ANALOG MAINS L2 GENERATOR DIGITAL MAINS L3 VOLTAGE CONVERTOR SENSING GEN. N & GEN. L1 CONDITIONING FREQUENCY SENSING FROM GENERATOR VOLTAGE COUNTER & TIMER PUSH LED DISPLAYS BUTTONS & INDICATORS FAILURE & CONTROL INPUTS EAOM-19 BLOCK DIAGRAM...
Page 43
10. User Defined Parameters List - 1 Prm. No. Definition of Parameter User Defined Value Mains voltage connection level Mains voltage disconnection level Mains voltage upper limit Alternator voltage lower limit Alternator voltage upper limit Speed lower limit Speed upper limit Number of starting attempts Engine cooling time Horn duration...