Installation - Carrier CRECOMZR067A01 Installation Instructions Manual

Small rooftop units 3 to 12.5 tons
Table of Contents

Advertisement

WIRING
HARNESS
ECONOMI$ER X
Fig. 3 — EconoMi$er
HVAC Unit (CRECOMZR067A01 Shown)
UNIT FILTER
RACK
ECONOMI$ER X
HOLD DOWN TAB
UNIT BASE
ECONOMI$ER X REAR FLANGE
Fig. 4 — EconoMi$er X Flange Installation
(CRECOMZR067A01 and CRECOMZR069A01)
5. Ensure EconoMi$er X assembly is square (tolerance
±
1
/
inch). Screw the EconoMi$er X to the unit along
32
both side flanges and bottom flange. See Fig. 3.
6.
Remove the red tape securing the relief dampers for ship-
ping purposes. Relocate the HH79AH001 dry bulb sen-
sor from its shipping location to its operating position;
see Fig. 1.
7.
If the EconoMi$er X assembly will be operating with an
enthalpy outside air sensor, remove the factory-installed
HH79AH001 dry bulb sensor from the front face of the
economizer (see Fig. 1) and install the accessory
enthalpy sensor HH57AC081 in the same location as the
dry bulb sensor. Connect the 2-wire gray harness with
plug from the EconoMi$er X assembly to the enthalpy
sensor. See wiring diagrams on pages 9 and 12. Refer to
"Installing Optional HH57AC081 Single Outside Air
Enthalpy Sensor" on page 13 for more details on
enthalpy settings.
HVAC UNIT FILTERS
INSERT
SCREW IN
ECONOMI$ER X
FLANGES
®
X Assembly Installed on
ECONOMI$ER X
ROOFTOP UNIT'S
12-PIN MALE PLUG
ECONOMI$ER X
12-PIN FEMALE PLUG
Fig. 5 — Connect EconoMi$er X Harness to Unit PL6
Economizer Harness
8.
Remove and save the 12-pin jumper plug from the unit
economizer harness located in the upper left corner of the
unit. Insert the EconoMi$er X plug into the unit wiring
harness. See Fig. 5.
NOTE: The 12-pin jumper plug should be saved for future use,
in the event that the EconoMi$er X is ever removed. The jumper
plug is not needed as long as the EconoMi$er X is installed.
9.
Remove the indoor blower access panel and the panel(s)
covering the unit control box. See Fig. 6.
CENTER POST
UNIT CONTROL
BOX PANEL(S)
Fig. 6 — Typical Indoor Fan Motor Access Panel
10. In the hardware kit provided with the EconoMi$er X
assembly is the HH63AW002 Jade controller (Honey-
well W7220). The controller is attached to a mounting
bracket and the EconoMi$er X harness is attached to the
controller. Mount the controller assembly on the left side
of the unit control box. Screw bracket to the control box
through pre-punched holes in control box. See Fig. 7.
4
INDOOR FAN MOTOR
ACCESS PANEL
Locations

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Crecomzr069a01Crecomzr071a01

Table of Contents