About This Guide

This guide contains step-by-step instructions for
setting up your D-Link Unshielded Patch Panel.
Please note that the model you have purchased
may appear slightly different from those shown in
the illustrations.

Product Overview

Front Panel
Figure 1. Unshielded Patch Panel Front
Color Coding Information
T568A
Pin 1
White/Green
Pin 2
Pin 3
White/Orange
Pin 4
Pin 5
White/Blue
Pin 6
Pin 7
White/Brown
Pin 8
Table 1. Wire Color Code
Installation
A. To connect a cable to the Unshielded Patch
Panel, first take the end of the cable wiring and
strip approximately 30 mm off the cable jacket.
(Figure 2)
B. Separate the wires into 4 pairs.
2
T568B
Pin 1
Green
Pin 2
Pin 3
Blue
Pin 4
Pin 5
Orange
Pin 6
Pin 7
Brown
Pin 8
Figure 2.
D-Link Unshielded Patch Panel Quick Installation Guide
C. Take off the support bar before punching
wires. (Figure 3)
Cut outside
White/Orange
D. Follow the IDC color code for T568A or
Orange
T568B wiring. (Table 1)
White/Green
Use the impact tool to punch in and
Blue
connect the wires to the IDC. (Figure 4)
White/Blue
Green
White/Brown
Brown
Support bar
E. Lock the support bar onto the rear of the
panel. (Figure 5)
Cable tie
F. Use a twist tie to secure the cable tightly
onto the support bar. Repeat this process
for each cable you wish to connect.
(Figure 6)
Ver. 1.00(WW) 2013/03/12 GAAHA1Y1100003
Figure 3.
Figure 4.
Figure 5.
Figure 6.