Electronic control unit ERM
Setting of DIL switches:
Adjustable filter constant
New condition
Filter constant
Controlled with Ø calculation
Unit size coding clutch / brake, see page 18
DIL switch setting
Jumper position: Jumper position "1" or "2"
(see 1.4, page 13) can activate further
functions.

3.4.4 Startup

1. The electronic control unit is disconnected.
2. Make sure that voltage is within the range given under
"1. Technical Data" ! (see page 6)
6057 758 101 - 2005-02
CAUTION
Filter time
7 8
Unpermitted voltage and polarity may damage the
0.5 sec
0 0
installation!
2.5 sec
0 1
1.5 sec
1 0
0.2 sec
1 1
DIL switches
1 2 3 4 5 6 7 8
0 1
0 1
0 1
0 1
10. Installation is ready for operation.
NOTE
Should the installation not function properly, consult
"4. Identification and causes of failure / corrective action"
(see page 38) !
33
3. Check polarity (plus / minus) !
4. Switch off operating voltage !
5. Connect the ERM !
6. Switch on operating voltage !
"Power" LED must light up.
"Ø contr." must flash.
7. Set max. roller speed Ø and production speed (> 3 Hz).
8. Push "set" key.
9. Release "set" key.
Reference Ø is accepted,