5 — SDO: Device Parameter Objects
name
Output Driver Mode 3000h
Output Max Value
Dither Period
Dither Amount
Driver Proportional
Gain
Driver Integral Gain 3005h
Nominal Battery
Analog Source
Enable
26

DEVICE PARAMETER OBJECTS

The parameters found in the 3000h CAN Object address range are shown in
Table 3. All these parameters have Read/Write (RW) SDO access, except for
the sub-index 00h in a parameter array, which is Read Only (RO) as indicated.

Table 3 Device Parameter Objects

-
index
sub
index
00h
01h – 06h
3001h
00h
01h – 06h
3002h
00h
01h – 06h
3003h
00h
01h – 06h
3004h
00h
01h – 06h
00h
01h – 06h
3010h
00h
3020h
00h
range
CaN
value
description
6
Length of this array (RO).
0 – 7
Binary value that sets each driver
0 – 7
to Input Only (0), Constant Current (1),
Constant Voltage (2), or Direct PWM (3)
Note: a
mode.
setting of 4
Adding 4 to Modes 1, 2, or 3 will enable
is non-valid.
the Driver Open Check (= 5, 6, 7).
Not applicable to Input Only mode.
6
Length of this array (RO).
Sets the maximum output that will be
Voltage Mode
0.0 – 80.0 V
commanded when the PDO command
0 – 800
is 100%. Could be a current, a voltage,
or a PWM % depending on the Mode
Current Mode
0.00 – 3.00 A
setting.
0 – 300
The value and range will be
automatically changed when
Direct Mode
0.0 – 100.0 %
the Driver Mode is changed.
0 – 1000
6
Length of this array (RO).
4 – 200 ms
Sets the time between dither pulses
4 – 200
for each output.
A Dither Period of 4 ms to 200 ms
Resolution = 2
provides a frequency range
of 250 Hz to 5 Hz.
6
Length of this array (RO).
0 – 0.50 A
Sets the amount (+/-) of dither
0 – 50
that will be added/subtracted
to the command. Only active when
the driver is in Constant Current mode.
6
Length of this array (RO).
1 – 100%
Proportional gain factor of the
0 – 1000
PI Current Controller.
6
Length of this array (RO).
1 – 100%
Integral gain factor of the
0 – 1000
PI Current Controller.
12 – 80V
Set to the nominal system/battery
120 – 800
voltage. This setting is used for detecting
both under and over voltage faults. See
Table 5 Troubleshoot Chart.
0 – 3
Turns on/off the current sources
0 – 3
on Analog 1 or 2.
LSB is for Analog 1 and next
is for Analog 2.
Upper 6 bits are not used.
(Use bit = 1 to turn on source.)
Curtis 1352 eXm Manual,
Rev. D