Download Print this page

Honeywell GSX Series Installation Instructions Manual page 19

Global explosion-proof safety switch

Advertisement

MICRO SWITCH GSX Series
Table 1. Specifications
Designation and
Utilization Category
AC15
A300
AC15
A500
AC15
A600
DC13
Q300
Rated thermal current
(Ith)
Sealing
Rated impulse withstand
(Uimp)
Pollution degree
Rated insulation voltage
(Ui)
Operating temperature
range
Short-circuit protective
device (type/maximum
rating)
Expected mechanical life 1,000,000 operations
Conditional short-circuit
current
Electrical rating for gold-
plated contacts
Low Voltage Directive 73/23/EEC, as amended by directive 93/68/EEC
Machinery Directive 98/37/EEC only as the directives relate to the components being used in a safety function
Sira 08ATEX1073X
IEC Ex SIR 08.0021X
IEC/EN60947-1, IEC/EN60947-5-1
MCTF (Mechanical Life): > 1,000,000 Cycles with Single Sided Confidence Limit of 100% *
MCTF (Electrical Life): > 25,000 Cycles with Single Sided Confidence Limit of 100% *
Highest SIL Capability: SIL3 (HFT:1), IEC 61508-2: 2010 * (* APPLICABLE ONLY FOR GSX***A** - * THROUGH GSX***D** - *)
Proof Test Interval: 1 Year
Rated Operational Current Ie (A) at Rated Operational Voltage Ue (V)
24 V
120 V
6 A
6 A
6 A
2,8 A
0,55 A
10 A
IP67; NEMA 1, 3, 4, 12, 13
2500 V
3
300 V, 500 V, 600 V
-40 °C to 70 °C [-40 °F to 158 °F]
Class J fuse (10 A/600 V)
1000 A
10 mA to 100 mA, 1 Vac/Vdc to 50 Vac/Vdc
240 V
380 V
3 A
3 A
1,9 A
3 A
1,9 A
0,27 A
50032072
ISSUE 10
480 V
500 V
1,5 A
1,4 A
1,5 A
1,4 A
Sensing and Internet of Things
600 V
1,2 A
19