York Predator ZT037 Technical Manual page 44

R-410a, zt series, 3 - 5 ton, 60 hertz
Hide thumbs Also See for Predator ZT037:
Table of Contents

Advertisement

5167821-YTG-J-0518
UNIT DESCRIPTION / MODEL
TEST CONFIGURATION
Indoor Blower Speed (RPM)
External Static Pressure (IWG)
Nominal Airflow (CFM)
Blower Motor BHP
Octave Center Freq. Hz
63
125
250
500
1000
2000
4000
8000
1. Differentials for Cooling Operation (IDB, COMP, & ODF) are logarithmically calculated from the horizontal flow sound test.
• Tested in accordance with AHRI Standard 260-2001. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning
Equipment.
• Testing datum includes effect of standard inlet air filters.
• Test duct dimension: 18 in. wide x 28 in. high x 8 ft. long, no elbows.
• Test duct termination is flush with reverberant room wall.
• Duct end (sound reflection) corrections included: (7.2, 3.4, 1.2, 0.4, 0.1, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 2k, 4k, 8k) Hz respectively.
Indoor Sound Power Levels (Vertical Ducted Discharge, High Static Belt Drive)
UNIT DESCRIPTION / MODEL
TEST CONFIGURATION
Indoor Blower Speed (RPM)
External Static Pressure (IWG)
Nominal Airflow (CFM)
Blower Motor BHP
Octave Center Freq. Hz
63
125
250
500
1000
2000
4000
8000
1. Requires driven pulley #AK-56, normal high static pulley is an #AK-69.
2. Differentials for Cooling Operation (IDB, COMP, & ODF) are logarithmically calculated from the horizontal flow sound test.
• Tested in accordance with AHRI Standard 260-2001. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning
Equipment.
• Testing datum includes effect of standard inlet air filters.
• Test duct dimension: 18 in. wide x 28 in. high x 8 ft. long, no elbows.
• Test duct termination is flush with reverberant room wall.
• Duct end (sound reflection) corrections included: (7.2, 3.4, 1.2, 0.4, 0.1, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 2k, 4k, 8k) Hz respectively.
44
1,039 - 5 Turns Open Equivalent
1.0
2,000
1.11
ID Blower
Cooling
1
Only (dB)
Operation
79
80
74
75
63
65
62
63
61
61
55
56
52
52
47
47
920 - 3.0 Turns Open Equivalent
1.0
1,200
0.68
ID Blower
Cooling
2
Only (dB)
Operation
81
82
78
78
69
70
67
68
62
63
60
61
61
61
54
55
ZT061 / 5 Ton / High Static Belt Drive
Vertical (Bottom Return) Ducted Inlet
1,143 - 3 Turns Open Equivalent
1.6
1,800
1.25
ID Blower
(dB)
Only (dB)
Operation
77
71
63
64
61
55
50
46
ZT037 / 3 Ton / High Static Belt Drive
Vertical (Bottom Supply) Ducted Discharge
1,074 - Fully Closed Equivalent
1.6
1,100
0.93
ID Blower
(dB)
Only (dB)
Operation
81
78
70
68
67
62
63
57
1,201 - 2 Turns Open Equivalent
Cooling
ID Blower
1
(dB)
Only (dB)
77
81
73
73
64
63
64
62
61
59
56
54
51
50
46
46
1,189 - 2.0 Turns Open Equivalent
Cooling
ID Blower
2
(dB)
Only (dB)
81
82
78
81
71
74
69
71
68
70
63
65
63
66
57
60
Johnson Controls Ducted Systems
2.0
1,600
1.39
Cooling
1
Operation
(dB)
81
74
65
62
59
55
50
46
1
1
2.0
1,000
1.09
Cooling
2
Operation
(dB)
82
81
74
71
71
66
66
61