Installation method (continued)
(2) Confirm that the pulse input switch (SW2-2) is set to "OFF".
(Set to "OFF" at time of shipment.)
Lossnay
Power supply
When using Mitsubishi Mr. Slim air conditioner with MA
Remote controller
Connect the interlocking cable connector side to CN2L on the circuit
board for the indoor Mr. Slim unit, then connect the lead wire side to
the 1 and 2 of the input terminal block (TM2) for the Lossnay exter-
nal controller input. (No polarity)
Always separate the power supply cable and the Slim-Lossnay
connection cable by 5 cm or more to prevent the unit from
malfunctioning.
The Slim-Lossnay connection cable is 0.25 m long. When wiring,
extend it as far as necessary.
Lossnay
External controller input (TM2)
1 2 3
Within 500 m
Note
The Lossnay remote controller (PZ-60DR-E, PZ-41SLB-E)
cannot be used with this system.
Use MA remote controller of Mr. Slim for switching Lossnay
ON/OFF or the fan speed.
The ventilation mode is "automatic ventilation".
The Slim-Lossnay connection cable may be extended to a
maximum length of 500m. (Extension cable specifications
are as detailed below)
Ensure that all connections are secure and that the appro-
priate insulation is provided.
Use extension cable sheathed PVC cable or cable 0.5 mm
to 1.0 mm
2
.
When the external device has a charged operating signal of
12 VDC or 24 VDC
Connect the operating signal (wire) from the external device via
the remote output to 1 and 2 on the external control input
terminal block (TM2). (No polarity)
Lossnay External control input (TM2)
123
Overall connection extension length
(Follow the operation manual for the external equipment.)
When the external device has an uncharged a-contact signal
Connect the operating signal (wire) from the external device via
the remote output to 1 and 3 on the external control input
terminal block (TM2).
8
Remote controller
(PZ-60DR-E or
PZ-41SLB-E)
External
Power supply
device
Operating switch for
external device
Slim-Lossnay connection cable
(Enclosed accessory)
CN2L
White
Mr. Slim (Indoor unit)
Red
Printed circuit board
2
2
0.5 mm
to 1 mm
sheathed PVC cable
External device
12 or 24 VDC
Lossnay External controller input (TM2)
12 3
CAUTION
If an optocoupler or any other type of polar coupler is used at
the uncharged a-contact, connect the positive side to 3 3 3 3 3 and
the negative side to 1 1 1 1 1 .
3
When interlocking with a pulse output device
(1) Move the pulse input switch [SW2-2] to the ON position.
(Refer to function settings 1 "Settings for pulse input".)
(2) Connect the pulse output device (i.e., building management sys-
tem) to the external control input terminal block [TM2].
A pulse width of at least 200 msec will be needed.
When using PZ-60DR-E, it can be set also from the remote controller.
Connecting methods vary depending on the types of pulse signal
Refer to Section 2 "When the external device has a charged
operation signal of 12 VDC or 24 VDC" or "When the external
device has an uncharged a-contact signal".
SW2
4
When operating multiple Lossnay units
(1) Connect from Lossnay Unit 1 to Lossnay Unit 2, and from Unit 2 to
Unit 3 and so on up to a maximum of 15 units using a transmission
cable (PVC insulated PVC jacketed and either between φ 0.65
and φ 1.2, or between 0.3 mm
(2) Change the setting on the main/sub switch (SW1) on the second
and subsequent Lossnay units to "Sub".
Lossnay
(Main)
Power
supply
2
Lossnay (Sub)
Power
supply
Lossnay (Sub)
Power
supply
MAX 15 units
CAUTION
Don't tighten screws of terminal block with a torque larger than
0.5 Nm. It could damage the PCB.
Note
Up to four 0.3 mm
be connected to one input terminal.
For other types of wire, up to two can be connected.
The operation signal and pulse signal can be connected to
the external device of the main Lossnay only.
Connect the power to each respective Lossnay unit.
When the LGH-150RX
operate at low fan speed even if extra low fan speed is selected.
0.5 mm
2
to 1 mm
2
sheathed PVC cable
External device
Uncharge a-contact
Within 500 m
ON
1
2
3
4
5
6
7
8
9 10
ON
OFF
2
and 1.25 mm
2
in cross section).
Main/Sub selection
Remote controller
switch
(PZ-60DR-E or PZ-41SLB-E)
(SW1)
Power
Main
External
supply
device
Operating switch
(Factory setting: main)
for external device
First Lossnay
TM4
1
2
Second
TM4
1
2
Lossnay
Transmission cable
2
stranded wires or φ 0.65 PVC wires can
and LGH-200RX
types are connected, they
5
5
Sub
Connect to
remote
controller
(PZ-60DR-E)
Connect
to third
Lossnay

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents