Getting Other Information and Publications These publications can help you install the air conditioner or heat pump. You can usually find these at your local library or purchase them directly from the publisher. Be sure to consult current edition of each standard. National Electrical Code ...
75 degree C cooper wire size, basic unit only. OPTIONAL FIELD INSTALLED HEATER PACKAGES ONLY TO BE USED WITH THE HEAT PUMP MODELS INDICATED OPTIONAL FIELD-INSTALLED ELECTRIC HEATER TABLE . r t & Time delay fuses or “HACR” type circuit breakers must be used for 60 and smaller sizes. Standard fuses or circuit breakers are suitable for sizes 70 and larger.
FIELD INSTALLED HEATER PACKAGES (OPTIONAL) These packaged heat pumps are manufactured without supplementary electric heaters. Supplementary heaters EH3P series (to fit PH1224, PH1230, and PH1236) are available for simple, fast, field installation. A separate field power circuit is required for the supplementary heaters.
PREFABRICATED ROOF CURB SPECIFICATIONS HEAVY GAUGE GALVANIZED WITH WOOD NAILING STRIP, WELDED/LEAKPROOF ONE PIECE CONSTRUCTION – READY TO INSTALL MIS-1177 *Duct Sizing Information Return Air Dimension “C” is length Return Air Dimension “H” is width MIS-1178 Manual 2100-344 Page FIGURE 1 CURB AND ROOF DETAILS Supply Air Dimension “C”...
LOCATION GENERAL The unit must be located outside, or in a well ventilated area. It must not be in the space being heated or cooled. A sound absorbing material should be considered if the unit is to be installed in such a position or location that might cause transmission of sound or vibration to the living area or adjacent buildings.
FIGURE 5 ROOF TOP APPLICATION (May also be required for ground level installations.) MIS-1176 FIGURE 6 SLAB MOUNTING AT GROUND LEVEL (Above 32° F Outside Temperature) MIS-1184 Manual 2100-344 Page...
CONDENSATE DRAIN TRAP It is very important to provide a trap in the condensate drain line to allow a positive liquid seal in the line and assure correct drainage from the coil condensate pan. Install condensate drain trap shown in Figure 7. Use drain connection size or larger.
WIRING – MAIN POWER Refer to the unit rating plate for wire sizing information and maximum fuse size. Each outdoor unit is marked with a “Minimum Circuit Ampacity”. This means that the field wiring used must be sized to carry that amount of current. If field installed heaters are added to the basic unit, a second separate power supply circuit will be required.
THERMOSTATS See specific wiring information for the different models, heater KWs, and voltages. No automatic changeover position – must be manually placed in heat or cool. Reversing valve remains energized at all times system switch is in heat position (except during defrost cycle). No pressure equalization noise when thermostat is satisfied on either heating or cooling.
THERMOSTAT INDICATOR LAMPS The red lamp marked “EM. HT.” comes on and stays on whenever the system switch is placed in Em. Ht. position. The green lamp marked “Check” will come on if there is any problem that prevents the compressor from running when it is supposed to be.
THREE PHASE SCROLL COMPRESSOR START UP INFORMATION Scroll compressors, like several other types of compressors, will only compress in one rotational direction. Direction of rotation is not an issue with single phase compressors since they will always start and run in the proper direction. However, three phase compressors will rotate in either direction depending upon phasing of the power.
SERVICE AND TROUBLESHOOTING SERVICE HINTS 1. Caution homeowner to maintain clean air filters at all times. Also, not to needlessly close off supply and return air registers. This reduces air flow through the system which shortens equipment service life as well as increasing operating costs.
CHECKING TEMPERATURE SENSOR CHECK OUT 1. Disconnect temperature sensor from board and from outdoor coil. 2. Use an ohmmeter and measure the resistance of the sensor. Also use ohmmeter to check for short or open. TEMPERATURE F vs RESISTANCE R OF TEMPERATURE SENSOR Manual 2100-344 Page 3.
SUCTION AND DISCHARGE TUBE BRAZING Compliant Scroll compressors have copper plated steel suction and discharge tubes. These tubes are far more rugged and less prone to leaks than copper tubes used on other compressors. Due to different thermal properties of steel and copper, brazing procedures may have to be changed from those commonly used.
COOLING HEATING Low side pressure ± 2 PSIG High side pressure ± 5 PSIG Tables are based upon rated CFM (airflow across the evaporator coil and should be found under section titled “Refrigerant Charge” elsewhere in manual. If there is any doubt as to correct operating charge being in the system, the charge should be removed, system evacuated, and recharged to serial plate instructions.