7 . Terminal 5 must be
connected to earth ground.
a. Use wire nuts to pass the
shield wire through the
electrical box with NO
connection to the device
terminal block or to local
ground.
b. Use shielded wire to
connect the switch wiring.
c. Tie the switch wiring shield
to terminal 5 or the local
earth ground.
8. For proprietary burglary
application (Refer to Figure 9):
a. Use an HTSW-1 tamper
switch to monitor the main
enclosure.
b. Monitor each HTRI-S/-R/-D
related to this application
continuously by using a
listed motion detector (to
prevent tampering).
9. In supervisory:
HTRI-S/-R draws 1mA
HTRI-D draws 1mA
MOUNTING
Siemens Building Technologies, Inc.
8 Fernwood Road
Florham Park, New Jersey 07932
Siemens Building Technologies
Fire Safety
LINE 1
TO NEXT
LINE 2
ADDRESSABLE DEVICE
LINE 1
FROM CONTROL PANEL
OR FROM PREVIOUS
LINE 2
ADDRESSABLE DEVICE
END OF LINE DEVICE
SEE NOTES 2 AND 8
SUPERVISED SWITCH
SEE NOTES 1, 5, 8 AND 9
SEE NOTE 7
LINE 1
TO NEXT
LINE 2
ADDRESSABLE DEVICE
LINE 1
FROM CONTROL PANEL
OR FROM PREVIOUS
LINE 2
ADDRESSABLE DEVICE
END OF LINE DEVICE
SEE NOTES 2 AND 8
SUPERVISED SWITCH
SEE NOTES 1, 5, 8 AND 9
SEE NOTE 7
Figure 9
Security Point (1076) Wiring Connections
Terminal 5 of the HTRI-S/-D/-R must be connected to a known good earth ground for
proper operation.
Addressable Interface SIEMENS Models HTRI-S, HTRI-D, and HTRI-R mount directly
into a (user supplied) double gang or 4 inch switchbox. Fasten the module to the
switchbox with the switchplate using the 2 screws provided.
A red LED will blink to indicate an off-normal input switch position and/or an internal
relay transfer.
Be sure to program the HTRI before fastening the switchplate to the unit.
4-INCH SQUARE BOX
2 1/8-INCHES DEEP
Figure 10
Mounting the HTRI-S/-R/-D
Siemens Building Technologies, Ltd.
2 Kenview Boulevard
Brampton, Ontario L6T 5E4 Canada
HTRI-S/-R
1
2
3
4
8
5
7
6
HTRI-D
1
2
3
4
8
5
7
6
DOUBLE GANG BOX
3 1/2-INCHES DEEP
SWITCHPLATE
5-INCHES SQUARE
(SUPPLIED)
NOTE:
WITH HTRI-S, TERMINALS
5 AND 6 ARE NOT USED.
RELAY CONTACTS
SEE NOTE 6
NOT USED
END OF LINE DEVICE
SEE NOTES 2 AND 8
SUPERVISED SWITCH
SEE NOTES 1, 5, 8 AND 9
SWITCHPLATE
5-INCHES SQUARE
(SUPPLIED)
P/N 315-033300-2