Siemens HTRI-S Installation Instructions page 3

Addressable switch interface modules

Advertisement

Wiring Entering Outlet Box
WIRING AT THE TERMINAL BLOCKS
Power Limited Wiring
Non-Power Limited Wiring
NOTES:
1. All supervised switches
must be held closed and/or
open for at least a quarter of
a second to guarantee
detection.
2. End of line device: 3.6K, 1/4W
resistor, P/N 140-820185. For
Canadian applications, use
Model EL -33 with 3.6K, 1/4W
resistor.
3. HTRI is polarity insensitive.
Line 1 and Line 2 can be
either line of the loop.
4. Electrical ratings:
Voltage maximum: 30 VDC
Current maximum:
1mA during polling
5. Supervised switch ratings:
Voltage maximum: 27 VDC
Current maximum: 3.5mA
during polling
Contact resistance maximum:
10 ohms
Maximum cable length:
200 feet (18 AWG)
C
:
0.02uF
Line to line
C
:
0.04uF
Line to shield
Max line size:
14 AWG
Min line size:
18 AWG
6. Relay contact ratings:
4A, 125 VAC resistive
4A, 30 VDC resistive
Inductive:
3.5A, 120 VAC (0.6 P .F .)
3.0A, 30 VDC (0.6 P .F .)
2.0A, 120 VAC (0.4 P .F .)
2.0A, 120 VAC (0.35 P .F .)
2.0A, 30 VDC (0.35 P .F .)
The relay is shown in
standby condition.
Siemens Building Technologies
Fire Safety
All power limited wiring must enter the outlet box separately from the electric light,
power, Class 1, or non-powered limited fire protection signaling conductors. For the
TRI-R, wiring to terminal block positions 1, 2, 3, 4, and 5 must enter the outlet box
separately from terminals 6, 7 , and 8.
Minimize the length of wire entering the outlet box.
(Refer to Figure 5) Wiring to positions
1, 2, 3, 4, and 5 is power limited.
Wiring to positions 6, 7 , and 8 is considered
non-power limited.
Ground shield ONLY at the specified
location on the Control Panel.
LINE 1
TO NEXT
LINE 2
ADDRESSABLE DEVICE
LINE 1
FROM CONTROL PANEL
OR FROM PREVIOUS
LINE 2
ADDRESSABLE DEVICE
END OF LINE DEVICE
SEE NOTE 2
SUPERVISED SWITCH
SEE NOTES 1 AND 5
SEE NOTE 7
Figure 6
HTRI-R Wiring
LINE 1
TO NEXT
ADDRESSABLE DEVICE
LINE 2
LINE 1
FROM CONTROL PANEL
OR FROM PREVIOUS
LINE 2
ADDRESSABLE DEVICE
END OF LINE DEVICE
SEE NOTE 2
SUPERVISED SWITCH
SEE NOTES 1 AND 5
SEE NOTE 7
Figure 7
HTRI-S Wiring
LINE 1
TO NEXT
LINE 2
ADDRESSABLE DEVICE
LINE 1
FROM CONTROL PANEL
OR FROM PREVIOUS
LINE 2
ADDRESSABLE DEVICE
END OF LINE DEVICE
SEE NOTE 2
SUPERVISED SWITCH
SEE NOTES 1 AND 5
SEE NOTE 7
Figure 8
HTRI-D Wiring
WIRES CONNECTED TO TERMINALS 1 THROUGH 5
TO ENTER/EXIT ELECTRICAL BOX OPPOSITE SIDE
FROM WIRES CONNECTED TO TERMINALS 6 THROUGH 8.
Figure 5
HTRI-R Power Limited Wiring
1
2
3
4
5
1
2
3
4
5
1
2
3
4
8
5
7
6
3
P
1
P
2
P
3
P
4
8
P
5
7
6
P = POWER LIMITED
N = NON-POWER LIMITED
8
RELAY CONTACTS
7
SEE NOTE 6
6
8
7
NOT USED
6
NOT USED
END OF LINE DEVICE
SEE NOTE 2
SUPERVISED SWITCH
SEE NOTES 1 AND 5
P/N 315-033300-2
N
N
N