Kikusui PCR-LE Quick Reference Manual
Kikusui PCR-LE Quick Reference Manual

Kikusui PCR-LE Quick Reference Manual

Advertisement

Quick Links

Main specifications
1P: Single-phase input/output, 1P3W: Single-phase three-wire output, 3P: Three-phase output, 3P3W: Three-phase three-wire input, 3P4W: Three-phase
four-wire input
TYP: Typical values that are representative of situations where the PCR-LE/PCR-LE2 Series operates in an environment with an ambient temperature of 23 °C.
Item
PCR
PCR
PCR
500LE
1000LE
2000LE
Input ratings (AC rms)
Voltage
1P
100 V input type: 85 Vac to 132 Vac,
200 V input type: 170 Vac to 250 Vac
3P3W
--
3P4W
--
Frequency
47 Hz to 63 Hz
Apparent power
Approx.
Approx.
Approx.
0.93 kVA
1.8 kVA
3.6 kVA
AC mode output ratings (AC rms)
Voltage
Output L range: 1 V to 150 V, Output H range: 2 V to 300 V
0.1 V
Resolution
Maximum
1P
5 A,
10 A, 5
20 A,
current(Output
2.5 A
A
10 A
L range, H
1P3W, 3P
---
range)
*1
Power capacity 1P
500 VA
1 kVA
2 kVA
1P3W
---
3P
Maximum peak current
Max. current (rms) × 4
(TYP)*2
Maximum reverse current
30 % of the max. current (rms)
*3
Frequency*1
1 Hz to 999.9
Hz*4
Resolution
0.01 Hz (1.00 Hz to 100.0 Hz), 0.1 Hz (100.0 Hz to 999.9 Hz)
DC mode output ratings
Voltage (output L range, H
1.4 V to 212 V, 2.8 V to 424 V
range)
Resolution
0.1 V
Maximum
1P
3.5 A,
7 A,
14 A,
current(Output
1.75 A
3.5 A
7 A
L range, H
1P3W
---
range)*5
Maximum instantaneous
Max. current (rms) × 3.6 (Limited by the rated output current's rms value)
current
Power capacity 1P
350 W
700 W
1.4 kW
1P3W
---
Output voltage waveform distortion ratio, Output voltage response speed
Output voltage
FAST
0.2 % or less
waveform
MEDIUM
0.3 % or less
distortion
ratio*6
Output voltage
FAST
20 μs (TYP)
response
MEDIUM
30 μs (TYP)
speed
*7
General
Input terminal
Inlet
M4
M5
Output terminal
M4
M4
M4
*1. When the output voltage is between 1 V and 100 V or 2 V and 200 V and the load power factor is between 0.8 and 1. When the output voltage is
between 100 V and 150 V or 200 V and 300 V, the output current is reduced by the output voltage. When the load power factor is between 0 and 0.8, the
output current is reduced by the load power factor. When the output frequency is between 1 Hz and 40 Hz, the output current is reduced by the output
frequency. *2. For capacitor-input rectifier loads, (at near the peak of the voltage waveform, excluding three-phase three-wire output). The peak current
that can be output decreases in accordance with the reduction in the absolute value of the instantaneous output voltage. *3. When the output voltage is
100 V or 200 V and the output frequency is between 40 Hz and 999.9 Hz (reverse current is -180 deg out of phase with the output voltage). *4. 1 Hz to 500
Hz when a 3P05-PCR-LE (500HZ LMT) is installed in the PCR-LE and on the PCR-LE2 500HZ LMT model (during three-phase output). *5. When the output
voltage is between 100 V and 212 V or 200 V and 424 V, the output current is reduced by the output voltage. *6. When the output voltage is between 80
V and 150 V or 160 V and 300 V and the load power factor is 1. *7. When the output voltage is 100 V or 200 V, the load power factor is 1, and the output
current changes from 0 A to the rated value and from the rated value to 0 A. *8. Three-phase three-wire or Three-phase four-wire input: M5 *9. Single-phase
three-wire or Three-phase input: M5
PCR
PCR
PCR
PCR
PCR
PCR
3000LE
4000LE
6000LE
9000LE
6000LE2
9000LE2
170 Vac to
--
170 Vac to
--
250 Vac
250 Vac
170 Vac to 250 Vac
187 Vac to 250 Vac (Phase voltage)
Approx.
Approx.
Approx.
Approx.
Approx.
Approx.
5.5 kVA
7.3 kVA
10.6 kVA
15.7 kVA
10.6 kVA
15.7 kVA
30 A,
40 A,
60 A,
90 A,
60 A,
90 A,
15 A
20 A
30 A
45 A
30 A
45 A
20 A,
30 A,
10 A
15 A
3 kVA
4 kVA
6 kVA
9 kVA
6 kVA
9 kVA
4 kVA
6 kVA
6 kVA
9 kVA
21 A,
28 A,
42 A,
63 A,
42 A,
63 A,
10.5 A
14 A
21 A
31.5 A
21 A
31.5 A
14 A,
21 A,
7 A
10.5 A
2.1 kW
2.8 kW
4.2 kW
6.3 kW
4.2 kW
6.3 kW
2.8 kW
4.2 kW
--
--
M8
M8
M8*8
M5
M8*8
M5
M5
M5
M8
M8
M8*9
M8*9
PCR-LE PCR-LE2
Quick Reference
PCR
PCR
PCR
12000LE2
18000LE2
27000LE2
Approx.
Approx.
Approx.
1
23 kVA
33 kVA
48 kVA
120 A,
180 A,
270 A,
18
60 A
90 A
135 A
19
40 A,
60 A,
90 A,
20 A
30 A
45 A
12 kVA
18 kVA
27 kVA
8 kVA
12 kVA
18 kVA
12 kVA
18 kVA
27 kVA
Name
1
OUTPUT key
2
Display
3
Numeric keypad
4
ON PHASE key
5
RANGE key
6
SYNC key
OFF PHASE key
7
8
KEYLOCK key
84 A,
126 A,
189 A,
9
RESET key
42 A
63 A
94.5 A
10
SLEEP key
28 A,
42 A,
63 A,
11
LOCAL key
14 A
21 A
31.5 A
+/- key
12
DIGIT key
13
8.4 kW
12.6 kW
18.9 kW
CLR key
14
ALM CLR key
5.6 kW
8.4 kW
12.6 kW
F key
15
PHASE key
0.5 % or less
50 μs (TYP)
M8
M8
M8
M8
M8
M8
Alarms/Trouble
When a protection function is activated, an alarm (ALM-xx) or a
trouble indication (TRBL-xx) is generated, and the output is turned
off.
Alarm: Press ALM CLR(SHIFT+CLR) to clear the alarm, and then fix
the problem that caused the alarm.
Trouble: To clear the trouble indication, turn the POWER switch off,
wait at least 5 seconds, and turn it back on. If the same trouble
persists, contact your Kikusui agent or distributor to request repairs.
Z1-006-102, IB027724
Sep. 2017
2
20
Function
Name
Turn output on and off
16
Display the settings/ measured value
Enter numeric values directly
17
Set the output on phase
18
Switch output voltage range
19
Set the synchronization function
20
Set the output off phase
Lock and unlock the keys
21
Reset the product
Set the sleep mode
22
Switch between remote and local mode
23
Switch the polarity of the voltage
The cursor moves to the left
24
Clear the numeric keypad input
25
Clear alarms
Set the frequency
Switch different displays during multiphase
operation (optional)
information.
Two-phase output setting PCR-
LE optional
Voltage compensation function
Harmonic current analysis
function
Generating special waveforms
(waveform bank)
Setting the output impedance
Setting soft starts (the voltage
rise time)
Fixing the internal Vcc
Selecting the response
Controlling the Output Using
The newest version of the
operation manual can be
downloaded from Kikusui website.
http://www.kikusui.co.jp/en
PCR-LE
PCR-LE2
manual
manual
3
15
16
17
4
5
6
7
8
9
10
11
12
13
14
21
22
23
24
25
19
Function
I key
Configure the current settings
I/P/λ-MEAS key
Switch the current/power measurement mode
V key
Configure the voltage settings
V-MEAS key
Switch the voltage measurement mode
ESC key
Cancel operations
Detachment button Detach the control panel
Function key
Correspond to the menus on display
MEMORY key
Save/Load settings from memory
OHTERS key
Configure advanced operation settings
Enable the functions that are indicated in the
SHIFT key
bottom row to the left of each key
ENT key
Apply settings
SIM key
Configure power line abnormality simulations
SEQ key
Configure sequence operations
OPR MODE key
Configure the operation environment settings
CONFIG key
Specify the configuration settings
T h e a c c o m p a n y i n g C D - R O M d e s c r i b e s t h e f o l l o w i n g
External Analog Signals
(Optional)
Remote control
Sequence tutorial
Options
Troubleshooting
Maintenance
Factory default settings
Alarms/ Trouble
Specifications
Table for power line abnormality
simulation settings
Table for sequence settings
MANUAL

Advertisement

loading
Need help?

Need help?

Do you have a question about the PCR-LE and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Kikusui PCR-LE

  • Page 1 Alarm: Press ALM CLR(SHIFT+CLR) to clear the alarm, and then fix Hz when a 3P05-PCR-LE (500HZ LMT) is installed in the PCR-LE and on the PCR-LE2 500HZ LMT model (during three-phase output). *5. When the output Setting soft starts (the voltage Alarms/ Trouble the problem that caused the alarm.
  • Page 2 The hold time DATABITS Data length Slope time 2 U VOLT*1 Voltage of U phase Single-phase, three-wire output or Three-phase output (PCR-LE optional) STOP BITS Stop bits MEMORY key Return time or the number V VOLT*1 Voltage of V phase...

This manual is also suitable for:

Pcr-le2