Staco Energy FLU-160-00 User Manual

Firstline p series maintenance bypass switch cabinet 160kva-250kva, 480v input/output with skru

Advertisement

FIRSTLINE P
Maintenance Bypass
Switch Cabinet
160kVA-250kVA, 480V Input/Output
With SKRU
USER MANUAL
003-2621

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the FLU-160-00 and is the answer not in the manual?

Questions and answers

Summary of Contents for Staco Energy FLU-160-00

  • Page 1 FIRSTLINE P Maintenance Bypass Switch Cabinet 160kVA-250kVA, 480V Input/Output With SKRU USER MANUAL 003-2621...
  • Page 2: Table Of Contents

    Table of Contents SECTION 1 .......................... 1 Introduction ........................1 Overview ........................... 1 Applicability ........................2 Part Numbers ........................2 Section 2 ..........................3 SAFETY WARNINGS ....................... 3 DANGER .......................... 3 WARNING ........................3 CAUTION ......................... 4 Section 3 ..........................5 Cabinet Setup ........................
  • Page 3: Section 1

    SECTION 1 Introduction Overview The FirstLine P Maintenance Bypass Switch Cabinet for 160 kVA, 200 kVA, 250 kVA with 480 V Input and Output is a steel cabinet that attaches to the side of the UPS cabinet, thereby extending the cabinet, and providing the maintenance bypass function. The cabinet has conduit attachment points at the top and the bottom for maximum flexibility in wiring the source and load power connections.
  • Page 4: Applicability

    Applicability This equipment can be applied to UPS models FLU-160-00, FLU-200-00, and FLU-250-00. These UPS models operate at 480 V, 60 Hz and can be wired as delta in and delta out (3 wire plus ground) or wye in and wye out (4 wire plus ground).
  • Page 5: Section 2

    SECTION 2 SAFETY WARNINGS IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS READ AND FOLLOW ALL SAFETY INSTRUCTIONS • Do not use outdoors. • Do not route wiring across or near hot surfaces. • Do not install near gas or electric heaters. •...
  • Page 6: Caution

    CAUTION The UPS associated with this equipment contains batteries. Batteries can present a risk of electrical shock or burn from high short circuit current. Observe proper precautions. Servicing should only be performed by qualified service personnel knowledgeable of batteries and the required precautions. Keep unauthorized personnel away from batteries. Read, understand, and follow all instructions in the ups manual before attempting any operations involving the battery.
  • Page 7: Section 3

    SECTION 3 Cabinet Setup This SECTION describes:  Equipment inspection  Floor loading and clearances  Removing and replacing the cabinet panels  Unloading the cabinet(s)  Attaching the cabinet to the UPS Inspecting the Equipment If any equipment has been damaged during shipment, keep the shipping and packing materials for the carrier or place of purchase and file a claim for shipping damage.
  • Page 8: Unloading The Cabinet(S)

    Unloading the Cabinet(s) The following tools are required for unloading the cabinet(s):  Wrenches for 3/8” lag bolts.  Forklift or pallet jack CAUTION The cabinets are heavy (see Table 2). Unloading the cabinets requires at least two people to safely remove the cabinets from the pallet. To remove the Maintenance Bypass Switch cabinet from the ship pallet: Make sure the forklift is rated for the cabinet weight.
  • Page 9: Attaching The Cabinet To The Ups

    Attaching the Cabinet to the UPS The Maintenance Bypass Switch cabinet was constructed so that it can be mounted to the side of the UPS cabinet if desired. To attach the Maintenance Bypass Switch Cabinet to the UPS Cabinet: 1. Remove right side panel of UPS and save hardware. 2.
  • Page 10: Section 4

    SECTION 4 Electrical Installation Overview Each of the pieces of equipment covered by this manual has four sets of power connections: 1. Input from the power source, typically, from the electric utility. 2. Power routed to the input of the UPS. If the bypass and rectifier inputs are powered from separate sources, the bypass input must be fed from the MBS.
  • Page 11 5. Select wire size in compliance with Table 3. 6. Recommended crimp terminal lugs are shown in Table 4. The power and neutral terminal pads, see Figure 4 and Figure 5, are provided with 3/8-16 bolts. REMOVABLE CONDUIT LANDING PLATE FOR POWER WIRING GROUND POWER TERMINAL PADS CONNECTIONS...
  • Page 12 Table 3 - Wire Size Requirements. *Wire must be rated 75°C or higher. Use copper conductors only. Minimum Required Minimum Input Wire Minimum Output Wire Ground Supply Rating Size Size Wire Size Breaker 500 kcmil or (2) 2/0 300 kcmil 3 AWG 300 A 500 kcmil or (2) 2/0...
  • Page 13 Wiring Installation 1. Switch off utility power to the distribution point where the UPS will be connected. Be absolutely sure that there are no hazardous voltages present. Use lockout/tagout procedures to assure safety. 2. Remove as many panels as needed for adequate access for wiring the cabinet. Open the front door of the MBS Cabinet.
  • Page 14: Control Connections

    Control Connections Four control connections must be made between the Maintenance Bypass Switch Cabinet (MBS) and the UPS in order to provide backfeed protection, a required safety feature The wiring to these low voltage (“ELV”) connections must be kept separated from the higher voltage wiring.
  • Page 15: Section 5

    SECTION 5 Operation Refer to the User's Manual for the UPS for instructions on operating the UPS part of the system. If the UPS is part of a parallel system, special operating instructions apply. Maintenance Bypass Switch (MBS) The purpose of the Maintenance Bypass Switch (MBS) is to facilitate servicing the UPS without removing power from the load.
  • Page 16 Common MBS operations: (refer to the UPS manual for UPS operations; BKR1, BKR2, BKR3 are part of the Maintenance Bypass Switch Cabinet; all other switches are part of the UPS) To transfer from normal mode on the UPS to maintenance bypass— 1.
  • Page 17 Need to get power to the load, but the condition of the UPS is uncertain— 1. Verify that the load is truly not powered. 2. Verify that the utility source is suitable (applying power to the load using the MBS is at the operator’s risk).
  • Page 18 Figure 7 - Circuit Breaker Sequence Label Table 7 - Maintenance Bypass Switch States Breaker 1 = Left hand breaker = UPS Input Breaker 2 = Center breaker = Bypass Breaker 3 = Right hand breaker = UPS Output Breaker Breaker Breaker State Name...
  • Page 19 Table 8 - Maintenance Bypass Switch State Change Procedures (refer to Table 9 for description of states) From State To State Procedure Normal Overlap 1. Select Manual Bypass Mode on UPS. 2. Verify load on bypass by observing front panel of UPS. 3.
  • Page 20: Section 6

    SECTION 6 Maintenance There are no wear items in the MBS that require periodic replacement. However, regular care will assure maximum availability of power. Keep the ventilation openings in the cabinet free of dust and debris. Wipe the cabinet exterior with a soft cloth, slightly dampened with water, to remove dust. Consider performing periodic infrared temperature measurements on the circuit breaker terminations.

This manual is also suitable for:

Flu-200-00Flu-250-00

Table of Contents