D. Check fuse on the indoor PCB Ass'y
Check fuse on indoor PCB
Ass'y for continuity
Check operation lamp to see if
light is ON
Measure resistance of primari
and secondary winding of
transformer
Indoor PCB Ass'y is detective.
E. Check TIMER on the remote control unit
Timer i turned On.Check to see
if is displayed on remote control
8-6-3 Only outdoor unit does not run
A Check setting temperature
COOL
Is room temperature too low?
Try to lower setting temperature by
temperature setting button
Try to use another remote
control unit
Remote control unit is defective
OK
Light is OFF
YES
NO
Outdoor unit still does
not run
OK
Measure resistance of indoor
and outdoor fan motor winding
Measure resistance of
compressor motor winding
Measure coil resistance of power
relay in outdoor unit.
Replace the fuse
Cancel the timer mode push the
buttom CLEAR
HEAT
Is room temperature too high?
Try to raise setting temperature by
temperature setting button
Try to use another remote
control unit
Remote control unit is defective
31
OK
OK
NO
Outdoor unit still does
not run
OK