8-6 Air Conditioner does not operate
8-6-1 Circuit breaker trips (or fuse blows).
A.
when the circuit breaker is set to ON, it is tripped soon.(resetting is not possible)
There is possibility of ground fault
Check insulation resistance
If resistance value is 2MΩor less, insulation is defective ( "NO")
1
Remove inter-unit wires from
terminal platea in outdoor unit
Mesaure insulation resistance of
outdoor unit.
2
Remove inter-unit wires from
terminal plate un outdoor unit.
Then, pull the power plug out of
the wall outlet.
Measure insulation resistance of
indoor unit
WARNING
NO
NO
29
Insulation of
outdoor unit is
defective
Measure insulation
resiatance of electical parts
in outdoor unit.
Insulation of
indoor unit is
detective.
Measure insulation
resiatance of electical parts
in indoor unit.