8-2. Air conditioner does not operate.

8-2-1. Circuit breaker trips (or fuse blows).
A. When the circuit breaker is set to ON, it is tripped soon. (Resetting is not possible.)
There is a possibility of ground fault.
Check insulation resistance.
If resistance value is 2MΩ or less, insulation is defective ("NO").
WARNING
*
Set circuit breaker to OFF.
1 Remove inter-unit wires from
terminal plate in outdoor unit.
Measure insulation resistance
of outdoor unit.
2 Remove inter-unit wires from
terminal plate in indoor unit.
Measure insulation resistance
of indoor unit.
Insulation of
NO
outdoor unit
is defective.
Measure insulation
resistance of electrical
parts in outdoor unit.
Insulation of
NO
indoor unit
is defective.
Measure insulation
resistance of electrical
parts in indoor unit.