2.3 Viewing the Event Log

The event log is a list by date/time of the last 400 events generated by iCOM for the thermal-
management unit.
On the User menu, touch Event Log.
The EVENT LOG for the cooling unit opens. Table 2.3 below describes the color-coded status
for each event.
NOTE: Depending on the type of thermal-managment unit, included components, and control settings
of your system, the options on your iCOM display may differ.
Table 2.3 Event status/type indicators
Indicator
Green dot
Yellow dot
Red dot
White dot with check-mark overlay Acknowledged event, the cause still exists.
White circle

2.4 Viewing Sensor Data

The Sensor Data panel lists the standard and optional sensors monitored by iCOM and the current
reading of each sensor.
Touch
The SENSOR DATA panel opens.
A secondary panel displays the DAILY SENSOR READING SUMMARY, which shows
temperature, humidity and dew-point readings for the cooling unit.
NOTE: Depending on the type of thermal-managment unit, included components, and control settings
of your system, the options on your iCOM display may differ.

2.5 Managing Run Hours for a Component

You can view the run hours for components on a cooling unit, set the total-run-time limit, and reset total
run hours to zero.
1.
Touch
The RUN HOURS panel opens and the current hours for each component are listed in the
Total Run Hours column.
To reset the total run hours to zero, see
2. Use the slider to set the total-run-time limit for each component, then touch Save.
The limits are set.
NOTE: Depending on the type of thermal-managment unit, included components, and control settings
of your system, the options on your iCOM display may differ.

2.5.1 Setting run hours to zero

1.
On the RUN HOURS panel, touch to check each box in the Total Run Hours column next to the
component(s) to reset.
The Set to Zero button becomes available.
2. Touch Set to Zero.
The total run hours for selected component(s) is set to zero.
22
Description
Message.
Unacknowledged warning event. See
Unacknowledged alarm event. See
Acknowledged event, the cause is cleared.
, then
> Sensor Data.
, then
> Total Run Hours.
Acknowledging Alarms
Acknowledging Alarms
Setting run hours to zero
on page 22.
on page 21.
on page 21.