Basic Operation - Altronix PT2724 Installation Manual

Two (2) channel 365 day 24 hr. timer/controllers
Table of Contents

Advertisement

PT2724 controls two independently operated dry form "C" relays. Relays can be programmed to: turn on (latch),
turn off (release latch) or pulse (momentary toggle) at a specified time and day (this is referred to as an event).
Events are programmed via the push buttons and LCD display. Events may be programmed to occur on any day
of the week at any time. In addition, events may be programmed as a block events that repeat at a specific time
on two (2) or more consecutive days (i.e. MO-FR, SU-TH, etc). Multiple combinations of individual and block
events may be programmed. Holiday exceptions are individually selected by date and will override all regularly
scheduled events.
Mode
Relay OFF
Relay ON
Disable
Pulse
Time is displayed in 24 hr. military format.
Terminal Legend
NO, C, NC, CH A
NO, C, NC, CH B
+ DC –
~ AC ~
+ BAT –
12VDC
FM
Fig. 1
+ DC –
AC
12-24 Volt
AC/DC input
PT2724

Basic Operation:

Output Relay Modes:
Status
De-energizes the relay until a relay ON event is detected.
Energizes the relay until a relay OFF event is detected.
Used to cancel an existing programmed event.
Momentarily energizes the relay for a selectable time period of 1 sec. to 15 secs.
Terminal Identification Table:
Function/Description
Dry Contact outputs used to switch controlled devices. When these relays are energized
(ON) the NC and C terminals are open and the NO and C terminals are closed. When
this relay is de-energized (Off) the NC and C terminals are closed and the NO and C
terminals are open.
AC or DC Input 12 to 24 volt. When using DC carefully observe polarity
12VDC stand-by battery input (battery leads provided).
When this terminal is connected to DC neg. (–) the "First Man in" feature is enabled. The
relay will remain in its present position until this connection is terminated. At that time
the relay will resume normal operation and latest scheduled events will occur.
+ BAT –
FM
12VDC
3V Lithium Battery Socket
SW2
RELAY ON
SU
(Altronix part # LB2032)
01:01
SW3
SET
ENTER
UP
DWN
- 3 -

Advertisement

Table of Contents
loading

This manual is also suitable for:

Pt2724e

Table of Contents